Operation and Programming

Chapter 5

5-13

Overload Protection Settings

0

115% of Parameter 7

% of Current

Parameter 6 = 1

0

25 Hz

50 Hz

60 Hz

140% of Rated Drive Output Current

Hz

Maximum Frequency

0

% of Current

Parameter 6 = 2

115% of Parameter 7

0

25 Hz

50 Hz

60 Hz

140% of Rated Drive Output Current

Hz

Maximum Frequency

69% of Parameter 7

104% of Parameter 7

96% of Rated Drive Output Current

84% of Rated Drive Output Current

0

% of Current

Parameter 6 = 3

115% of Parameter 7

0

15 Hz

50 Hz

60 Hz

140% of Rated Drive Output Current

Hz

Maximum Frequency

69% of Parameter 7

84% of Rated Drive Output Current

Overload

Protection

Overload

Protection

Overload

Protection

Parameter 07 -- Overload Current
Units

= Amps

Range

= 000.1/500.0

Factory Setting = None

Parameters 6 and 7 will work in conjunction if Parameter 7 matches the
rated amps located on the motor nameplate, and Parameter 6 is set to 1, 2
or 3. When Parameter 6 is set to 0, the setting of Parameter 7 will have no
effect on drive operation. The overload current value for Parameter 7 may
be set in 0.1A increments.