Aux interlock enable – Rockwell Automation 1333 Drive, 3/4-5HP, 230-575V Series D User Manual
Page 71
Operation and Programming
Chapter 5
5-28
Aux Interlock Enable
Parameter
21
-- Auxiliary Interlock
Units
= Code
Range
= 0/1
Factory Setting = 0
To enable drive operation, terminal 16 and logic common at the Control
and Signal Wiring Terminal Block must be jumpered. This parameter sets
the function of terminal 16 and logic common when a normally closed
auxiliary interlock is installed in its place.
If set to 0, when the auxiliary contact opens:
•
The drive will coast-to-stop, display fault
AU
, and store the fault in
Fault Buffer Parameters 59-62.
•
Fault Contact CR3 on the Control Board will change state to provide a
fault signal at terminals 22-24 at the Control and Signal Wiring Terminal
Block.
If set to 1, when the auxiliary contact opens:
•
The drive will coast-to-stop and display
AS
. Since
AS
is not a fault, it
will not be stored in Fault Buffer Parameters 59-62.
•
Since
AS
is not a fault, Fault Contact CR3 on the Control Board will not
change state to provide a fault signal at terminals 22-24.