Operation and Programming

Chapter 5

5-8

Accel and Decel Settings

Parameter

01

-- Acceleration Time 1

Units

= Seconds

Range

= 0000/1600

Factory Setting = 005.0

This parameter determines the time that it will take the drive to accelerate
over a 60 Hz change in frequency. From 0 to 0.5 Hz, the accel rate is
effectively zero. From 0.5 Hz to maximum output frequency, the accel rate
set by Parameter 1 will remain constant. The total time it will take the drive
to accelerate from 0 to maximum drive output frequency is:
Total time = (Maximum Drive Output Frequency

×

Parameter 1)

÷

60.

If set to 0000, the drive will enter 40 ms but display 0000.

From 00.10-1000 seconds, this parameter sets the accel time value in 0.1
second increments.

From 1000-1600 seconds, this parameter sets the accel time value in 1
second increments.

Accel Settings

0

n

o

it

a

r

e

l

e

c

c

A

0.5

60 Hz

Output Frequency

Time

40mS

50 Hz

Parameter 1

Parameter 3 = 50Hz

Parameter 3 = FF
Parameter 15 = 120Hz

0

n

o

it

a

r

e

l

e

c

c

A

0.5

60 Hz

Output Frequency

Time

40mS

50 Hz

Parameter 1

Parameter 3 = 60Hz

0

n

o

it

a

r

e

l

e

c

c

A

0.5

60 Hz

Output Frequency

40mS

50 Hz

Parameter 1

120 Hz

Time