Drive supplied contact settings – Rockwell Automation 1333 Drive, 3/4-5HP, 230-575V Series D User Manual

Page 72

Advertising
background image

Operation and Programming

Chapter 5

5-29

Drive Supplied Contact Settings

Parameter

22

-- CR1 Select

Units

= Code

Range

= 1/2/3

Factory Setting = 1

This parameter sets the function of drive supplied contact CR1. CR1 is a
normally open contact located at terminals 19 and 20 on the Control and
Signal Wiring Terminal Block.

If set to 1, the N.O contact will close when the drive is within

±

2 Hz of the

run or jog set speed.

If set to 2, the N.O contact will close when the drive is at 140% of rated
drive output current or 125% of the current set in Parameter 7.

If set to 3, the N.O contact will close when the run or jog output frequency
is greater than the CR1 Frequency set by Parameter 24.

Parameter

23

-- CR2 Select

Units

= Code

Range

= 0/1/2/3

Factory Setting = 0

This parameter sets the function of drive supplied contact CR2. CR2 is a
normally open contact located at terminals 20 and 21 on the Control and
Signal Wiring Terminal Block.

If set to 0, the N.O contact will close when the drive receives a run or jog
start signal.

If set to 1, the N.O contact will close when the drive is within

±

2 Hz of

run or jog set speed.

If set to 2, the N.O contact will close when the drive is at 140% of rated
drive output current or 125% of the current set in Parameter 7.

If set to 3, the N.O contact will close when the run or jog output frequency
is greater than the CR2 Frequency set by Parameter 25.

Advertising