Preventive Maintenance and
Troubleshooting Common Drive Problems

Appendix B

B-14

6. The drive will not accelerate to maximum speed -- No fault is displayed.

The maximum allowable drive output frequency will be determined by the

lowest programmed value of any of the following parameters:

Parameter 3 Frequency Range

Parameter 15 Maximum Frequency

Parameter 51 Upper Frequency Clamp

Parameter 53 Bias Frequency -- If Parameter 53 is Higher Than

Parameter 54

Parameter 54 Gain Frequency -- If Parameter 54 is Higher Than

Parameter 53

Is Parameters 3 Frequency Range and/or 15 Maximum Frequency set high

enough to allow the drive to accelerate to maximum speed?

Reset Parameters 3 and/or 15.

Yes

No

No

Is Parameter 51 Upper Frequency Clamp set to a value lower than the

required maximum frequency?

Reset Parameter 51 to maximum frequency.

Yes

No

Contact your nearest AĆB representative for application assistance.

No

Yes

Are Parameters 42Ć45 programmed to exclude maximum frequency?

Reprogram Parameters 42, 43 and/or 44 to a value below the maximum

frequency. Reprogram Parameter 45 to a bandwidth that will not include the

maximum frequency value.

Yes

Is this an inverse speed follower application?

To program the drive for an inverse speed follower application, set Parameter

53 to the maximum frequency required and Parameter 54 to the minimum

frequency required.

Yes

Yes

Is Parameter 53 Bias Frequency set to a higher value than Parameter 54 Gain

Frequency (standard setting for inverse speed follower applications)?

If an inverse speed follower is required, reprogram Parameter 53 to maximum

frequency. If an inverse follower is not required, reprogram Parameters 53

and 54 as required.

No

Yes

Is Parameter 53 Bias Frequency set to a lower value than the required

maximum frequency?

Reset Parameter 53 to maximum Frequency.