Caution – Rockwell Automation 1333 Drive, 3/4-5HP, 230-575V Series D User Manual

Page 32

Advertising
background image

Installation and Wiring

Chapter 4

4-15

If You Use

200/208/230V AC, 1ĆPhase Input Voltage

Power

Recommended

Rating

Wire

Wire

Recommended

Code

Group ❶

Size ❷

Torque ❸

ZAA

2

14 AWG (2.5mm

2

)

9 In-lbs (1.02N-m)

AAA

2

14 AWG (2.5mm

2

)

9 In-lbs (1.02N-m)

YAA

2

14 AWG (2.5mm

2

)

9 In-lbs (1.02N-m)

BAA

2

12 AWG (4.0mm

2

)

9 In-lbs (1.02N-m)

CAA

2

10 AWG (6.0mm

2

)

9 In-lbs (1.02N-m)

DAA

2

8 AWG (10.0mm

2

)

10 In-lbs (1.13N-m)

EAA

2

8 AWG (10.0mm

2

)

10 In-lbs (1.13N-m)

Wire group number chart, page 4-6.

CAUTION :

230/208VA.C.

Input Voltage Only

Use 75 Degree C

AWG Copper Wire

Torque to

Lb-in

(Power Terminal Block Cover)

Select from the following drive input fuses.

Drive Rating ZAA

Fuse Size 15AFuse Type 600V Class K5 UL Listed or Equivalent

Drive Rating AAA

Fuse Size 15AFuse Type 600V Class K5 UL Listed or Equivalent

Drive Rating YAA

Fuse Size 15AFuse Type 600V Class K5 UL Listed or Equivalent

Drive Rating BAA

Fuse Size 30AFuse Type 600V Class K5 UL Listed or Equivalent

Drive Rating CAA Fuse Size 40AFuse Type 600V Class K5 UL Listed or Equivalent
Drive Rating DAA Fuse Size 70AFuse Type 600V Class K5 UL Listed or Equivalent
Drive Rating EAA

Fuse Size 80AFuse Type 600V Class K5 UL Listed or Equivalent

Advertising