Installation and Wiring

Chapter 4

4-16

+BUS -BUS

FAA or GAA 1ĆPhase

Power Terminal Block Wiring

jC

1333

Dynamic Brake

Earth

Ground

GND

GND

jA

Motor

jB

Earth

Ground

AC Incoming Line

W/

T

3

R/

L

1

S/

L

2

T/

L

3

U/

T

1

V/

T

2

User supplied drive input fuses.

Motor disconnecting means including branch circuit, short circuit, and ground-fault protection.

S/

L2

and T/L3

Input AC line Terminals are not phase sensitive.

For drives rated FAA or GAA, nominal 1-phase input voltage is
200/208/230V AC, 50/60 Hz.

Branch disconnect and short circuit protection is not part of the standard
1333 and must be supplied by the user. Drive input fuses are required to
provide component protection against malfunction of electronic circuits.

U/

T1,

V/

T2,

W/

T3

Connect the motor leads to these terminals.

+ BUS, - BUS

DC bus terminals are reserved for the 1333 Dynamic Brake Option. Refer
to the 1333 Dynamic Brake Option instructions for installation and
connection details.

GND

Two ground terminals have been provided in the drive. Either one of these
terminals must be connected to earth ground or the ground of the building
electrical system. The motor frame must also be connected to earth ground.
Refer to the motor installation instructions for specific details.