Load Initial Configuration Values

Chapter 7

7-38

Profile Pressure Alarm Setpoint

(FCC57, SCC57, TCC57, LPC57, FOC57, SOC57, TOC57, OSC57, EAC57)

The QDC module compares real-time clamp (or ejector) pressure against this
entry when executing the appropriate profile. The QDC module sets an alarm
bit (SYS05-B12, B13, B14, B15, SYS06-B09 B10, B11, B12, B13 respect-
ively) any time clamp (or ejector) pressure equals or exceeds this entry
during execution of the respective profile. A zero entry inhibits this alarm.

Important: EAC57 serves as the pressure alarm setpoint for both ejector
advance and ejector retract.

Enter 0 for each Profile Pressure Alarm Setpoint. A detailed discussion of
these setpoints is presented in chapter 10 to assist you in selecting the correct
final values required by your application. Refer to Section 3 of the Plastic
Molding Module Reference Manual (pub.1771-6.5.88) for more information.

After entering all values into the 10 configuration worksheets, use the same
PLC data table entry and download procedure presented in chapter 4.

1.

Enter all worksheet values into your PLC-5 data table.

Important: Be sure that you have not altered any setpoints, and that you
have entered each and every setpoint exactly as on the worksheets.

2.

Use the procedure described in chapter 4 to download command
blocks to the QDC module. For your convenience, we repeat
download information from chapter 4.

Important: Do not download companion blocks at this time.

Block to

Download:

ProĆSet 600

Block ID.:

ProĆSet 600

Download Bit B21/:

FCC

03

2

SCC

04

3

TCC

05

4

LPC

06

5

CPC

07

6

FOC

17

17

SOC

18

18

TOC

19

19

OSC

20

20

OPC

21

21

EAC

22

22

ERC

23

23

EPC

24

24

Enter and Download your

Worksheet Values

Advertising