Rockwell Automation 1771-QDC, D17716.5.87(Passport) CLAMP AND EJECT MODE User Manual
Page 37
Select Output 1 Range with bits 01, 00
Select Output 2 Range with bits 03, 02
Select Output 3 Range with bits 05, 04
Select Output 4 Range with bits 07, 06
Output Range
-10 to +10 vdc
0
0
0 to +10 vdc
0
1
4 to 20 mA
1
0
Not connected
1
1
Code:
Your value
Required initial value
loaded by ProĆSet 600
0 or 1
Configure the QDC Module's
Inputs and Outputs
Chapter 3
3-4
Worksheet 3ĆC
Selecting Output Ranges for your Valves
Control Word MCC04ĆBxx
15
14 13 12 11
10
09 08 07 06 05 04 03 02 01 00
ProĆSet 600 Addr. B35/bit
575 574 573 572 571 570 569 568 567 566 565 564 563 562 561 560
Value
1
1
1
1
1
1
1
1
Example: If you select 0-10 vdc for all four output ranges,
MCC04 = 11111111 01010101.
Important: Software input/output selections must match the jumper
settings for each respective input/output.