Span Your Clamp and Ejector Valves

Chapter 9

9-13

What You Have Accomplished
The valve spanning procedure you just completed has:

defined the range of pressure available during First, Second and Third

Clamp Close

informed the QDC module of the signal level needed to drive the

selected clamp pressure valve(s) for any requested open-loop pressure:

% of Signal Level Entered In:

Drives the selected valve to Produce:

FCC43, SCC43, TCC43

Pressure (usually 0) in FCC41, SCC41, and TCC41

FCC44, SCC44, TCC44

Pressure in FCC42, SCC42, and TCC42

Now, for all open-loop pressure-controlled First, Second, and Third clamp
close profiles, the QDC module:

drives the selected clamp pressure valve between the signal limits

imposed by FCC43 and FCC44, or SCC43 and SCC44, or TCC43 and
TCC44

assumes a linear relationship between clamp pressure and the signal

outputs

Set Pressure Alarm Setpoints

After spanning your Clamp Close pressure valve(s), set your Clamp Close
maximum pressure alarms (FCC57, SCC57, TCC57) equal to values you
feel should not occur during the respective Clamp Close profiles. Make
sure none of these values are greater than their respective Clamp Close
Maximum Pressure Control Limits (FCC42, SCC42, TCC42). Entering a
value of 0 disables these alarms.

Download changes to the QDC module. If necessary, refer to the