Enter Your Final SensorĆconfiguration Values Here

Configure the QDC Module's

Inputs and Outputs

Chapter 3

3-11

Complete the procedure for configuring the QDC module to match its
sensors by spanning them over their intended range with the machine in
operation. Here we describe how you determine:

clamp position sensor values
ejector position sensor values
clamp pressure sensor values
ejector pressure sensor values

In the procedures that follow, measure and record:

minimum and maximum positions
corresponding signal values
minimum and maximum pressures
corresponding signal values

After determining these values, write them down on Worksheet 3-E.

Important: You must complete this configuration before proceeding to
any other chapters on module configuration.

Worksheet 3ĆE

Final SensorĆconfiguration Values

Input

Control Word ProĆSet 600 Addr.

Value

Description

Units

1

MCC37

N41:33

0

Minimum Ejector Position

Ejector Axis Measured from zero

1

MCC38

N41:34

Maximum Ejector Position

Ejector Axis Measured from zero

1

MCC39

N41:35

Analog Signal @ Min Ejector Position

Input Signal Range

2

MCC40

N41:36

Analog Signal @ Max Ejector Position

Input Signal Range

2

2

MCC45

N41:41

0

Minimum Ejector Pressure

Ejector Pressure

3

MCC46

N41:42

Maximum Ejector Pressure

Ejector Pressure

3

MCC47

N41:43

Analog Signal @ Min Ejector Pressure

Input Signal Range

2

MCC48

N41:44

Analog Signal @ Max Ejector Pressure

Input Signal Range

2

3

MCC23

N41:19

0

Minimum Clamp Position

Clamp Axis Measured from zero

1

MCC24

N41:20

Maximum Clamp Position

Clamp Axis Measured from zero

1

MCC25

N41:21

Analog Signal @ Min Clamp Position

Input Signal Range

2

MCC26

N41:22

Analog Signal @ Max Clamp Position

Input Signal Range

2

4

MCC31

N41:27

0

Minimum Clamp Pressure

Clamp Pressure

3

MCC32

N41:28

Maximum Clamp Pressure

Clamp Pressure

3

MCC33

N41:29

Analog Signal @ Min Clamp Pressure

Input Signal Range

2

MCC34

N41:30

Analog Signal @ Max Clamp Pressure

Input Signal Range

2

1

Incremental Distance

2

Input Signal Range

3

Pressure

00.00 to 99.99 Inches

00.00 to 10.00V dc or

0000 to 9999 PSI

000.0 to 999.9 Millimeters

01.00 to 05.00V dc or

000.0 to 999.9 Bar

04.00 to 20.00MADC

Complete your Sensor

Configuration