Chapter 2

2-10

Figure 2.5

Shielding SingleĆended Outputs

Connect the cable shield

to earth ground at the valve

amplifier

QDC Module Output

9

8

Customer Valve Amplifier

Input

Ground

Chassis Ground

17182

+

ground the cable shields to a low-impedance earth ground of less than

1/8 ohm

do not connect any ground to input common (terminal 14) except as

specified below under Grounding Exceptions

place high-voltage class A wiring and low-voltage class B wiring in

separate grounded conduits

in parallel runs, separate the class A and B conduit by at least 1 foot

where conduit runs must cross, cross them at right angles

For additional grounding recommendations, refer to the Allen-Bradley
Programmable Controller Wiring and Grounding Guidelines (pub. no.
1770-4.1).

Exceptions

If you experience unacceptable electrical noise interference, then try one or
both of the following alternative grounding connections:

connect the input cable shield to input common (terminal 14) after

disconnecting the shield from the transducer

connect the output cable shield to output common (terminal 8, 6, 4,

and/or 2) after disconnecting it from the valve amplifier