Configure the QDC Module's

Inputs and Outputs

Chapter 3

3-10

ATTENTION: As soon as you enable set-output operation, the
QDC module’s outputs drive the connected valves according to
the values you entered into DYC09 - DYC12 (Pro-Set 600
words N41:121 - N41:124). Be sure these values RESULT IN
NO MOVEMENT until you adjust them one-at-a-time with
your programming terminal in the procedures that follow.

Actuating the Clamp and Ejector with SetĆoutput Operation

1.

Enter values that result in no motion in these DYC words:

Output:

In Data Word:

At ProĆSet 600

Address:

1

DYC09

N41:121

2

DYC10

N41:122

3

DYC11

N41:123

4

DYC12

N41:124

2.

Enable set-output operation by entering a 1 in DYC01-B08 (Pro-Set
600 address B35/392). The QDC module sets outputs 1 - 4 to
percentage values that you entered in DYC09 - DYC12 respectively.

3.

With your programming terminal, slowly increase the %-output value
of one output as you observe the corresponding movement.

Important: The DYC is constantly transferred to the QDC module by
Pro-Set 600 software, so changes you make to %-output values are
immediately implemented.