Install the QDC Module

Chapter 2

2-12

Figure 2.6

Typical PLC Power Distribution with Interlocks

Incoming
AC

L1

L2

L3

1FU

2FU

3FU

H

FUSE

Disconnect

To Motor
Starters

L1

L2

L3

H

Back-Panel
Ground Bus

Enclosure
Wall

Grounding Electrode
Conductor to
Grounding Electrode
System

Connect
When
Applicable

Equipment
Grounding
Conductors

User DC

Supply

CRM

To DC I/O
Devices

+

Output
Module
Wiring
Arm

Input
Module
Wiring
Arm

Output
Device

Input
Device

I/O Chassis

10907ĆI

Power Supply

L

N

1

GND

CRM

Start

Use any number
of E-Stop switches
in Series

CRM

CRM

1

4

H

3

H

2

Step-down

Transformer

X

1

X

2

To minimize EMI generation, you should connect a suppression network: for 120V AC, use Allen-Bradley
cat. no. 700-N24; for 220/240V AC, use cat. no. 599-KA04.

To minimize EMI generation, you should connect a suppression network: for 120V AC, use Allen-Bradley
cat. no. 599-K04; for 220/240V AC, use cat. no. 599-KA04.

For a power supply with a groundable chassis, this represents connection to the chassis only. For a power supply
without a groundable chassis, this represents connection to both the chassis and the GND terminal.

In many applications, a second transformer provides power to the input circuits and power supplies for isolation from the
output circuits.

1

2

3

4

1

2

3

4

** See WARNING for Interlock Wiring Instructions **

5

5

Reference the current NEC code and ANSI B151.1 for additional wiring guidelines.

To minimize EMI generation, suppression networks should be connected across coils of electromagnetic devices.