Troubleshoot with LED's

Chapter 11

11-3

The following table shows the meaning of the QDC module’s LEDs. The
QDC module monitors its own operation and reports detected conditions
by illuminating its LED’s in the following combinations:

Table 11.A

LED Indicator Conditions

ACTIVE FAULT

COMM

Condition:

We recommend that you:

Flashing Off

Off

PowerĆup. The QDC module has completed its powerĆup diagnosĆ

tics, the QDC module hardware and firmware are OK, and the QDC

module is awaiting download of the MCC block.

Download the MCC. ProĆSet 600 downloads the

MCC when you switch your PLC from program

mode to run mode.

Flashing Red

Yellow

Software Error. The QDC hardware and firmware are OK, the last

BTW received by the QDC module had a recognizable Block ID, but

the last MCC received by the QDC module contained a programĆ

ming error.

Use the MCC download procedure in chapter 3 to

correct any MCC programming errors.

Flashing Red

Off

Software Error. The QDC hardware and firmware are OK, but the

last BTW received by the QDC module did not have a recognizable

Block ID, and the last MCC received by the QDC module contained

a programming error.

1) Use the MCC download procedure in chapter 3

to correct any MCC programming errors.

2) Verify Block ID's in your PLC BTW data files.

Flashing Flashing Flashing You put the Run/Calibrate jumper (E1) in the Calibrate position.

Put jumper E1 in the Run position (chapter 2).

Green

Off

Yellow

Normal operation. The QDC hardware and firmware are OK, no

programming errors exist, and the last command data block

received by the QDC module had a recognizable Block ID.

Nothing.

Green

Off

Off

Software Error. The QDC hardware and firmware are OK, no proĆ

gramming errors exist, but the last command data block received by

the QDC module did not have a recognizable Block ID.

Verify Block ID's in your PLC Block transfer write

data files.

Green

Red

Yellow

Limited operation. The QDC hardware and firmware are OK, the

last command data block received by the QDC module had a recĆ

ognizable Block ID, but a programming error(s) exists.

Use the download procedure outlined in chapter 4

to determine and correct programming errors.

Green

Red

Off

Software Error. The QDC hardware and firmware are OK, but a

programming error(s) exists, and the last command data block

received by the QDC module did not have a recognizable Block ID.

1) Use the download procedure in chapter 4 to

determine and correct programming errors.

2) Verify Block ID's in your PLC Block transfer

write data files.

Off

Off

Flashing Communications Error. The QDC hardware and firmware are OK,

but the module is not completing continuous transmission of status

data blocks to the host PLC processor. The QDC module is inoperĆ

able until continuous BTR communication is reĆestablished with the

host PLC processor.

1) Verify your PLC is in run mode.

2) Reseat your QDC module in the I/O chassis.

3) Check for PLC ladder programming problems.

Off

Red

Yellow

or Off

Hardware fault. The QDC module is inoperable.

1) Cycle power to the QDC module.

2) Replace the QDC module and return it for

factory repair.

The QDC module was calibrated at the factory before shipment. We
recommend that you re-calibrated it every two years. Use the calibration
procedure in the Reference Manual, publication 1771-6.5.88 dated
November 1992, or return it to the factory with this order number:
1771-QDC/(Rev Letter) – CAL.