Configure the QDC Module's

Inputs and Outputs

Chapter 3

3-7

Use this download procedure now and later in this chapter. The procedure
requires you to complete the following general steps:

enter MCC values into the PLC-5 data table
download them to the QDC module (PLC-5 processor in run mode)
correct any data entry (programming) errors

Next we describe the general steps:

Enter MCC Values into Your PLCĆ5 Data Table

With your programming terminal, enter values from Worksheet 3-A thru
Worksheet 3-D into your PLC-5 data table as follows:

1. Switch the PLC-5 processor to program mode.

2. Display your PLC-5 data table.

3. Locate the data file for storing the MCC block. PLC-5 data table

word addresses are listed on the worksheets.

4. Enter the value for each word and bit.

When you enter bit selections in words prefixed with file identifier B
(example: B34), the PLC-5 processor automatically switches the radix to
binary format so you can conveniently enter binary data.

Download MCC Values to the QDC Module

To download the MCC block to the QDC module, switch the PLC-5
processor from program to run mode. Pro-Set 600 software downloads the
MCC block to the QDC module for you.

Important: You can verify that the MCC block was successfully down-
loaded or that you made a data entry (programming) error by evaluating
the following words that Pro-Set 600 software continuously reports to the
PLC-5 processor.

If:

And:

Then:

SYS01ĆB08 = 1

(B34/8)

N/A

QDC module accepted a valid MCC.

SYS19ĆB00 = 1

(B34/288)

SYS61 = 1

(ID code for MCC block

stored in N40:213)

You made a programming error in MCC.

Read the error code in SYS62 (N40:214) , and

look up the error in Section 2 of QDC Module

Reference Manual, publication 1771Ć6.5.88.