Enter Your PressureĆalarm and TimeĆdelay Values Here

Configure the QDC Module's

Inputs and Outputs

Chapter 3

3-19

Set Up Maximum Pressure Alarms and Time Delays

The QDC module continuously monitors clamp and ejector pressure
inputs. When it detects that the pressure equals or exceeds a preset
pressure alarm setpoint, the QDC module sets an alarm bit. A setpoint of
zero disables the associated alarm.

To guard against nuisance alarms caused by noise spikes or pressure
transients, you can set a time-delay so the QDC module must monitor
continuous excessive pressure for an amount of time before setting the
high pressure alarm. A setpoint of zero disables this delay.

Configure the QDC module for pressure alarms as follows:

1.

Determine these values for clamp and/or ejector pressure alarms:

pressure-alarm setpoint
time-delay setpoint

2.

Record non-zero setpoints on Worksheet 3-G for the pressure alarms
and time delays you want to use.

3.

Download them to the QDC module using the procedures presented
earlier in this chapter.

Worksheet 3ĆG

PressureĆalarm and TimeĆdelay Setpoints

Control Word

ProĆSet 600 Addr. Value

Description

Units

MCC35

N41:31

Clamp PressureĆalarm Setpoint

Clamp Pressure

2

MCC36

N41:32

ClampĆpressure TimeĆdelay Setpoint

Time Measured in Seconds

1

MCC49

N41:45

Ejector PressureĆalarm Setpoint

Ejector Pressure

2

MCC50

N41:46

EjectorĆpressure TimeĆdelay Setpoint

Time Measured in Seconds

1

1

Time

2

Pressure

00.00 to 00.99 Seconds

0000 to 9999 PSI

000.0 to 999.9 Bar