Delete unused alarm triggers – Rockwell Automation 193 Drives and Motion Accelerator Toolkit Quick Start User Manual

Page 128

Advertising
background image

128

Rockwell Automation Publication IASIMP-QS019E-EN-P - August 2013

Chapter 5

FactoryTalk View ME Configuration

Delete Unused Alarm Triggers

Follow these steps to delete any alarm triggers for hardware devices not used in your application. This could
improve performance of your PanelView Plus terminal communication.

1.

Expand the Alarms folder.

2.

Double-click Alarm Setup.

The Alarm Setup dialog box opens.

3.

Click the Triggers tab.

4.

Select any unused alarm trigger tags from the Select trigger organizer.

Unused trigger tags are any associated devices not configured in your Logix Designer project.

For the Widg-O-matic application example, these alarm triggers are used, so all other trigger tags can be
removed.

5.

Click Remove.

6.

Repeat

step 4

and

step 5

for all unused trigger tags.

7.

Click OK in the Alarm Setup dialog box to save edits.

IMPORTANT

Deleting Unused Alarm Triggers is optional and applies only if you have imported the Alarm Setup file in the last section.

Alarm Triggers Used

PowerFlexAlarmTrigger

ModuleAlarmTrigger

CIPMotionTrigger

K300AlarmTrigger

Advertising