Controller, Network, and Device Configuration Without the DMAT Wizard

The Module Definition dialog box opens.

7.

From the Time Sync Connection pull-down
menu, choose Time Sync and Motion.

8.

Click OK to close the Module Definition dialog box.

9.

Click Yes when prompted to confirm your module
definition changes.

10.

Click OK to close the New Module dialog box.

Your new module appears under the I/O
Configuration folder in the Controller Organizer.

Configure the Sercos Module

Follow these steps to configure sercos communication,
for Kinetix 6200, Kinetix 6000, Kinetix 6000M, Kinetix 2000, Kinetix 7000, or Ultra3000 sercos drives used in
your application.

1.

Right-click I/O Configuration in the Controller Organizer and choose New Module.

The Select Module dialog box opens.

2.

Expand the Motion category and select
1756-M

xxSE or 1768-M04SE as appropriate

for your actual hardware configuration.

In this example, the 1756-M16SE module is
selected.

3.

Click OK.

IMPORTANT

Time Sync functionality is what enables motion control on an Ethernet network. Without this setting, you won’t be able to
run your motion application.