Rockwell Automation Publication IASIMP-QS019E-EN-P - August 2013

323

Controller, Network, and Device Configuration Without the DMAT Wizard

Appendix G

12.

Verify your device configuration and save the file.

Refer to the Bulletin 193 EtherNet/IP Communications Auxiliary User Manual,

193-UM014

, for details on

how to configure parameters.

SMC-50 Soft Starter Configuration

SMC-50 soft starter configuration includes these procedures.

Update SMC-50 Add-On Profiles

Add SMC-50 Devices to your Logix Designer Project

Configure SMC-50 Devices

Update SMC-50 Add-On Profiles

Add-On profiles (AOP) are available for download at the Custom Downloads Add-On Profiles website:

https://download.rockwellautomation.com/esd/download.aspx?downloadid=addonprofiles

Follow these steps to download SMC-50 Add-On profiles.

1.

Login to the Custom Download Add-On Profiles website.

The Custom Download Files dialog box opens.

IMPORTANT

You must set the following parameters in the E3 Plus overload relay or the AOI does not function properly in your Logix Designer
application:
Param 59, Output Assembly = 105
Param 60, Input Assembly = 100
Param 61, Assy Word 0 Param = 21 (supplies status of Inputs and Outputs)
Param 62, Assy Word 1 Param = 4 (supplies Avg current)
Param 63, Assy Word 2 Param = 14 (supplies Trip Status)
Param 64, Assy Word 3 Param = 15 (supplies Warning Status)

IMPORTANT

The SMC-50 Add-On Profiles are independent of RSLogix 5000 software or Logix Designer application releases. Update your
SMC-50 Add-On Profiles to make sure your application runs correctly.