Machine Module

The machine module contains the high level control for the entire machine. The machine module was built
around a simple state machine that you can customize to fit most applications. The machine module broadcasts
out commands and receives feedback information from each of the application and device modules. Based on the
feedback information, the machine will react accordingly.

In addition, the machine module provides a high level interface with the HMI, accepting commands like Start,
Stop, and Clear Faults. It provides status info to the HMI terminal like current state of the machine (for example,
RUNNING versus STOPPED).

Machine States

By default, the machine program module operates based on this overall state diagram.

Machine State Diagram

The machine module uses the Transitional States to move between Permanent States. Typically, the machine
only remains on a Transitional State for brief period of time. If the machine module detects an error during a
Transitional State or if the application or device modules fail to transition within an allotted time (10 seconds by
default), the machine module issues an ABORT command. The fail safe transition timer makes sure the overall
machine does not become stuck in a Transitional State. It also helps to provide diagnostic information to
determine which module is not transitioning properly.

RESETTING

STOPPING

STARTING

RUNNING

START

The machine can go from any state in the shaded box to STOPPING.

IDLE

(enabled)

STOPPED

(disabled)

RESET

STOP

ABORT

ABORTING

ABORTED

CLEAR

CLEARING

The machine can go from any state

in the solid box to ABORTING.

Transitional State

Permanent State

Machine

Command