Specifications, Operating power, Power consumption – Winco DGC-2020 User Manual

Page 13: Battery ride through, Current sensing, 1 aac current sensing, Figure 1-1. dgc-2020 style chart

Advertising
background image

9400200990 Rev B

DGC-2020 General Information

1-3

Figure 1-1. DGC-2020 Style Chart

For example, if a DGC-2020 style number is 51BNBMEAH, the controller would have the following
characteristics and operating features.
5 5 Aac current sensing inputs
1 50/60 hertz nominal generator frequency
B 3 fixed-function output contacts and 12 programmable output contacts
N No RS-485 communication port
B Battery backup for real-time clock during losses of control power
M Internal dial-out modem—US version
E Enhanced generator protection (undervoltage, phase imbalance, overcurrent, overvoltage,

overfrequency, and underfrequency)

A Auto-synchronizer
H LCD heater

SPECIFICATIONS

Operating Power
Nominal:

12 or 24 Vdc

Range:

6 to 32 Vdc (Withstands cranking ride-through down to 6 Vdc
for 500 ms.)

Terminals:

3 (+), 2 (–), 1 (chassis ground)

Power Consumption
Sleep Mode:

5W with all relays non-energized

Normal Operational Mode:

7.9W - Run mode, LCD heater off, 3 relays energized

Maximum Operational Mode:

14.2W - Run mode, LCD heater on, 6 relays energized

Battery Ride Through
Withstands cranking ride-through down to 0 V for 50 ms.

Current Sensing
Burden:

1 VA

Terminals:

68, 69 (A-phase)

71,

72

(B-phase)

74,

75

(C-phase)

1 Aac Current Sensing
Continuous Rating:

0.02 to 1.0 Aac

Advertising