Modem setup (optional), Dial-out, Dial-in – Winco DGC-2020 User Manual

Page 62

Advertising
background image

4-12

DGC-2020 BESTCOMSPlus Software

9400200990 Rev B

A

Enable ECU Support: Check box to enable ECU support.

B

Enable DTC Support: Check box to enable DTC support.

C

CANBus Address: Accepts an address number from 0 to 253 in increments of 1.

D

ECU Config: Standard, Volvo Penta, or MTU MDEC.

E

Speed Select: Primary or Secondary.

F

Accelerator Position: Adjustable from 0 to 100% in 1% increments.

G

Select MDEC module type: Can Module 201, 302, 303, or 304.

H

MDEC speed demand switch: Analog CAN, Analog ECU, Up Down ECU, Up Down Can, Frequency, or

No CAN Demand.

I

MDEC engine RPM request: Adjustable from 1,400 to 2,000 in increments of 1.

J

Output Select: Fuel Contact or Pre-start Contact.

K

Pulsing: Enable or Disable.

L

Engine Shutdown: Adjustable from 1 to 60 s in 1 s increments.

M

Pulse Cycle Time: Adjustable from 1 to 60 s in 1 s increments.

N

Settling Time: Adjustable from 5,500 to 30,000 ms in 1 ms increments.

O

Response Timeout: Adjustable from 1 to 60 s in 1 s increments.

Modem Setup (Optional)

DGC-2020 controllers with style number xxxxxMxxx are equipped with an internal telephone modem that
has dial-in and dial-out capability. The modem gives the DGC-2020 the ability to dial up to four telephone
numbers

A

and annunciate user-selected conditions to specified pagers

B

. These user-selected conditions

include

C

:

• Auxiliary Input 1 Closed

• ECU Low Coolant Level Alarm

• Auxiliary Input 2 Closed

• Emergency Stop Alarm

• Auxiliary Input 3 Closed

• High Coolant Temp Pre-Alarm

• Auxiliary Input 4 Closed

• kW

Overload

Pre-Alarm

• Auxiliary Input 5 Closed

• Loss of ECU Coms Alarm

• Auxiliary Input 6 Closed

• Loss of Generator Voltage Sensing Alarm

• Auxiliary Input 7 Closed

• Low Battery Voltage Pre-Alarm

• Auxiliary Input 8 Closed

• Low Coolant Temp Pre-Alarm

• Auxiliary Input 9 Closed

• Low Fuel Alarm

• Auxiliary Input 10 Closed

• Low Fuel Pre-Alarm

• Auxiliary Input 11 Closed

• Low Oil Pressure Alarm

• Auxiliary Input 12 Closed

• Low Oil Pressure Pre-Alarm

• Auxiliary Input 13 Closed

• MPU Speed Sender Fail Alarm

• Auxiliary Input 14 Closed

• Oil Pressure Sender Fail Alarm

• Auxiliary Input 15 Closed

• Overcrank

Alarm

• Auxiliary Input 16 Closed

• Overspeed

Alarm

• Battery Overvoltage Pre-Alarm

• Scheduled Maintenance Pre-Alarm

• Coolant Temp Sender Fail Alarm

• Switch Not in Auto

• Cooldown Timer Active

• Weak Battery Voltage Pre-Alarm

Dial-Out

The DGC-2020 uses telelocator alphanumeric protocol (TAP) version 1.7 when communicating with
paging companies. This data format

D

specifies seven data bits with even parity. If required, eight data bits

with no parity may be specified.

The message string sent by the DGC-2020 can be limited to a length supported by the receiving pagers

E

.

If a message to be transmitted by the DGC-2020 exceeds the pager message limit, the DGC-2020 will
make multiple calls to transmit the complete message.

Dial-out messages are sent by the DGC-2020 at a user-defined interval

F

. This interval gives an operator

the opportunity to dial into the DGC-2020. A second user-defined interval

G

determines how frequently

dial-out attempts are made following a dial-out failure.

Dial-In

When the DGC-2020 modem shares a line used for voice communication, the number of rings

H

required

for the modem to answer can be increased to allow time for an operator to answer an incoming telephone
call.