Frequency protection, Underfrequency, Overfrequency – Winco DGC-2020 User Manual

Page 76

Advertising
background image

4-26

DGC-2020 BESTCOMSPlus Software

9400200990 Rev B

Figure 4-24. BESTCOMSPlus Voltage Protection Settings

A

Undervoltage Pickup: Adjustable from 70 to 576 Vac in 1 Vac increments.

B

Undervoltage Activation Delay: Adjustable from 0 to 30 s in 0.1 s increments.

C

Undervoltage Alarm Configuration: None, Alarm, or Prealarm.

D

Undervoltage Inhibit Frequency: Adjustable from 20 to 400 Hz in 1 Hz increments.

E

Undervoltage Low Line Scale Factor: Adjustable from 0 to 3.000 in increments of 0.001.

F

Overvoltage Pickup: Adjustable from 70 to 576 Vac in 1 Vac increments.

G

Overvoltage Activation Delay: Adjustable from 0 to 30 s in 0.1 s increments.

H

Overvoltage Alarm Configuration: None, Alarm, or Prealarm.

I

Overvoltage Low Line Scale Factor: Adjustable from 0 to 3.000 in increments of 0.001.

J

Phase Imbalance Pickup: Adjustable from 5 to 100 Vac in 1 Vac increments.

K

Phase Imbalance Activation Delay: Adjustable from 0 to 30 s in 0.1 s increments.

L

Phase Imbalance Alarm Configuration: None, Alarm, or Prealarm.

Frequency Protection

Two sets of frequency protection settings are provided: one for underfrequency (81U) and one for
overfrequency (81O).

Underfrequency

An underfrequency condition is annunciated when the generator frequency decreases below the 81U
pickup setting

A

for the duration of the 81U activation delay setting

B

. An underfrequency annunciation can

be user-selected to trigger a pre-alarm

C

(warning) or alarm

C

(shutdown). An underfrequency annunciation

can also be user-configured to close a programmable output.

A voltage-based inhibit setting

D

prevents an 81U trip from occurring during an underfrequency condition

associated with system startup.

Overfrequency

When the generator frequency increases above the 81O pickup setting

E

for the duration of the 81O

activation delay setting

F

, an overfrequency condition is annunciated. An overfrequency annunciation can

be user-selected to trigger a pre-alarm

G

(warning) or alarm (shutdown). An overfrequency condition can

also be user configured to close a programmable output.