Alarm configuration, Pre-alarms, High fuel level – Winco DGC-2020 User Manual

Page 70: Low battery voltage, Weak battery voltage

Advertising
background image

4-20

DGC-2020 BESTCOMSPlus Software

9400200990 Rev B

Figure 4-20. BESTCOMSPlus Configurable Outputs Settings

A

Label Text: An alphanumeric character string with a maximum of 16 characters.

ALARM CONFIGURATION

DGC-2020 alarms and pre-alarms can be used to annunciate system, genset, and engine sender
conditions. The description of the alarm configuration settings is organized as follows:
• Pre-Alarms

• Alarms

• Sender

Failure

Pre-Alarms

A pre-alarm is annunciated when a condition programmed to trigger a pre-alarm is met. When a pre-alarm
condition exists, it is annunciated (flashed) on the LCD, the front panel Alarm indicator flashes on and off
and the Horn output (if programmed and enabled) alternates between an energized and de-energized
state. The audible alarm is reset by pressing the front panel Alarm Silence pushbutton. When a pre-alarm
condition ceases to exist for pre-alarms other than weak battery, all displayed annunciations are reset
automatically. A weak battery pre-alarm condition is reset through the front panel by navigating to the
Alarms-Status, Pre-Alarms screen, scrolling through the list of pre-alarms until “Weak Battery” is
displayed, and pressing the Reset key.

Active pre-alarms for oil pressure, fuel level, coolant temperature, and battery voltage are displayed on
the main display of the LCD. The LCD annunciates an active pre-alarm by alternating the pre-alarm
message with the normally displayed data. All other pre-alarms are individually displayed, in sequence,
by scrolling through the LCD pre-alarms list.

Each DGC-2020 pre-alarm is described in the following paragraphs. Pre-alarms may be enabled and
adjusted in BESTCOMSPlus or through the front panel HMI.

BESTCOMSPlus pre-alarm settings (DGC-2020, Alarm Configuration, Pre-Alarms) are illustrated in
Figure 4-21.

High Fuel Level

High fuel level pre-alarm settings

A

consist of an enable/disable setting and a threshold setting. If enabled,

a high fuel level pre-alarm occurs when the metered fuel level increases above the threshold setting.

Low Battery Voltage

Low battery voltage pre-alarm settings

B

consist of an enable/disable setting, a threshold setting, and an

activation time delay. If enabled, a low battery voltage pre-alarm occurs when the battery voltage
decreases below the threshold setting for the duration of the activation time delay. The threshold setting
range is based on the nominal battery voltage setting on the BESTCOMSPlus System Settings tab (DGC-
2020, System Parameters, System Settings).

Weak Battery Voltage

Weak battery voltage pre-alarm settings

C

consist of an enable/disable setting, a threshold setting, and an

activation time delay. If enabled, a weak battery voltage pre-alarm latches during engine cranking when
the battery voltage decreases below the threshold setting for the duration of the activation time delay. The
threshold setting range is based on the nominal battery voltage setting on the BESTCOMSPlus System
Settings tab (DGC-2020, System Parameters, System Settings).