Winco DGC-2020 User Manual

Page 168

Advertising
background image

B-10 DGC-2020

Modbus

Communication

9400200990 Rev B

Holding

Register

Parameter Range

Read/Write

Supported

Data

Format

Units

40049 Threshold

3-100

R

W

PSI

LOW BATTERY VOLTAGE PRE-ALARM

40050 Enable

0-1

R

W

0 =Off
1 =On

40051 Threshold

60-120 (12V)
120-240 (24V)

R W

.1 Volts DC

40052

Pre-alarm Activation Time Delay

1-10

R W

Seconds

WEAK BATTERY VOLTAGE PRE-ALARM

40053 Enable

0-1

R

W

0 =Off
1 =On

40054 Threshold

40-80 (12V)
80-160 (24V)

R W

.1 VoltDC

40055

Pre-alarm Activation Time Delay

1-10

R W

Seconds

40056-59 RESERVED

HIGH COOLANT TEMP ALARM

40060 Enable

0-1

R

W

0 =Off
1 =On

40061

Threshold

100-280

R W

Degrees F

40062

Arming Delay after Crank
Disconnect

60 R

W

Seconds

LOW OIL PRESSURE ALARM

40063 Enable

0-1

R

W

0 =Off
1 =On

40064 Threshold

3-100

R

W

PSI

40065

Arming Delay after Crank
Disconnect

5-15 R

W

Seconds

OVERSPEED ALARM

40066 Enable

0-1

R

W

0 =Off
1 =On

40067

Threshold

105-140

R W

% of Rated

40068

Alarm Activation Time Delay

0-500

R W

MilliSec

40069-71 RESERVED

CRANKING PARAMETERES

40072

Cranking Style

0-1

R W

0=Contin.
1=Cycle

40073

Number of Crank Cycles

1-7

R W

40074

Cycle Crank Time

5-15

R W

Seconds

40075

Continuous Crank Time

1-60

R W

Seconds

40076

Crank Disconnect Limit

10-100

R W

% of Rated

40077

Pre-crank Delay

0-30

R W

Seconds

SYSTEM MONITOR

40078

Remaining Cooldown Time

0-60

R -

Minutes

40079 RESERVED

40080

Active Speed Signal Sources

1-4

R -

1=MPU
2=ALT
3=GEN
4=NONE

40081

Sender Failure Alarm Code

individual bits
are 0 or 1

R -

b0=High Coolant Temperature
b1=Oil Pressure
b2 Fuel Level
b3=Generator Voltage Sensing
b4=Magnetic Pick-up
b5-b7 not used

Advertising