Table conventions, Legacy parameter table – Winco DGC-2020 User Manual

Page 166

Advertising
background image

B-8 DGC-2020

Modbus

Communication

9400200990 Rev B

MAPPING - DGC 2020 PARAMETERS INTO MODICON ADDRESS SPACE

Table Conventions

Table B-3 uses the conventions outlined in this section.

The “Data Format” column uses the following abbreviations:

• DP - Double Precision
• TP - Triple Precision
• FP – Floating Point

Data formatted in Double Precision uses a 2 register group designated (a) and (b) and is defined as
follows:

• Register (a) - 2 hi-order bytes
• Register (b) - 2 lo-order bytes

Data formatted in Triple Precision uses a 3 register group designated (a), (b) and (x). It is defined as
follows:

• Register (a) - 2 hi-order bytes
• Register (b) - 2 mid-order bytes
• Register (x) - 2 lo-order bytes

Other register groups using the (a), (b), etc. designators are an ordered data group of consecutive ASCII
characters or data bytes.

Legacy Parameter Table

The DGC-2020 maps all legacy parameters previously associated with the DGC-500 and DGC-1000 into
the Holding Register address space (40000 to 41999). Query address N will access the Holding Register
N+1. The Data Format is Integer type data unless identified otherwise in the Data Format column.