DGC-2020 Time Overcurrent Characteristic Curves

9400200990 Rev B

Table A-1. 51 Time Characteristic Curve Constants

Trip Characteristic Constants

Curve

Selection

Curve Name

A B C N K

S1

S, S1, Short Inverse

0.2663

0.03393

1.0000

1.2969

0.0280

S2

S2, Short Inverse

0.0286

0.02080

1.0000

0.9844

0.0280

L1

L, L1, Long Inverse

5.6143

2.18592

1.0000

1.0000

0.0280

L2

L2, Long Inverse

2.3955

0.00000

1.0000

0.3125

0.0280

D

D, Definite Time

0.4797

0.21359

1.0000

1.5625

0.0280

M

M, Moderately Inverse

0.3022

0.12840

1.0000

0.5000

0.0280

I1

I, I1, Inverse Time

8.9341

0.17966

1.0000

2.0938

0.0280

I2

I2, Inverse Time

0.2747

0.10426

1.0000

0.4375

0.0280

V1

V, V1, Very Inverse

5.4678

0.10814

1.0000

2.0469

0.0280

V2

V2, Very Inverse

4.4309

0.09910

1.0000

1.9531

0.0280

E1

E, E1Extremely Inverse

7.7624

0.02758

1.0000

2.0938

0.0280

E2

E2, Extremely Inverse

4.9883

0.01290

1.0000

2.0469

0.0280

A

A, Standard Inverse

0.01414

0.00000

1.0000

0.0200

0.0280

B

B, Very Inverse (I

2

t)

1.4636 0.00000 1.0000 1.0469 0.0280

C

C, Extremely Inverse (I

2

t)

8.2506 0.00000 1.0000 2.0469 0.0280

G

G, Long Time Inverse (I

2

t)

12.1212

0.00000 1.0000 1.0000 0.0280

F

Fixed Time

0.0000 1.00000 0.0000 0.0000 0.0280


∗ Curve F has a fixed delay of one second times the Time Dial setting.

TIME OVERCURRENT CHARACTERISTIC CURVE GRAPHS

Figures A-1 through A-16 illustrate the characteristic curves of the DGC-2020. Table A-2 cross-
references each curve to existing electromechanical relay characteristics. Equivalent time dial settings
were calculated at a value of five times pickup. A drawing number is provided in the caption of each
graph.