9400200990 Rev B

DGC-2020 Modbus

Communication

B-27

Holding
Register

Parameter Range

Read/Write
Supported

Data
Format

Units

43752

Remote Start

0-1

R W

A value of 1 will invoke the Remote

Start

43754

Remote Stop

0-1

R W

A value of 1 will invoke the Remote

Stop

43756

Run Mode

0-1

R W

A value of 1 will invoke the Run Mode

43758

Off Mode

0-1

R W

A value of 1 will invoke the Off Mode

43760

Auto Mode

0-1

R W

A value of 1 will invoke the Auto Mode

43762 RESERVED

43764

Gen Breaker Open

0-1

R W

A value of 1 will open the Gen Breaker

43766

Gen Breaker Close

0-1

R W

A value of 1 will close the Gen Breaker

43768

Mains Breaker Open

0-1

R W

A value of 1 will open the Mains

43770

Mains Breaker Close

0-1

R W

A value of 1 will close the Mains

43772 RESERVED

43774

Virtual Input 1 Close

0-1

R W

A value of 1 will close the Virtual Input 1

Switch

43776

Virtual Input 1 Open

0-1

R W

A value of 1 will open the Virtual Input 1

Switch

43778

Virtual Input 2 Close

0-1

R W

A value of 1 will close the Virtual Input 2

Switch

43780

Virtual Input 2 Open

0-1

R W

A value of 1 will open the Virtual Input 2

Switch

43782

Virtual Input 3 Close

0-1

R W

A value of 1 will close the Virtual Input 3

Switch

43784

Virtual Input 3 Open

0-1

R W

A value of 1 will open the Virtual Input 3

Switch

43786

Virtual Input 4 Close

0-1

R W

A value of 1 will close the Virtual Input 4

Switch

43788

Virtual Input 4 Open

0-1

R W

A value of 1 will open the Virtual Input 4

Switch

43790-998 FUTURE

USE

PROTECTION

44000-34 RESERVED

44036-248 FUTURE

USE

44250

3 Phase Overcurrent Pickup

18-118 1A
90-7750 5A

R W

(Sec Amps / 100) in increments of 1

44252

3 Phase Overcurrent Time Dial

0-99

R W

(Units / 10) in increments of 1

44254

3 Phase Overcurrent Curve

0-16

R W

0 = S1 Curve
1 = S2 Curve
2 = L1 Curve
3 = L2 Curve
4 = D Curve
5 = M Curve
6 = I1 Curve
7 = I2 Curve
8 = V1 Curve
9 = V2 Curve
10 = E1 Curve
11 = E2 Curve
12 = A Curve
13 = B Curve
14 = C Curve
15 = G Curve
16 = F Curve

44256

3 Phase Overcurrent Alarm
Configuration

0-2 R

W

0 = None
1 = Alarm
2 = Pre-Alarm

44258

1 Phase Overcurrent Pickup

18-118 1A
90-7750 5A

R W

(Sec Amps / 100) in increments of 1

44260

1 Phase Overcurrent Time Dial

0-99

R W

(Units / 10) in increments of 1