5 aac current sensing, Voltage sensing, Contact sensing – Winco DGC-2020 User Manual

Page 14: Terminals, Engine system inputs, Fuel level sensing, Coolant temperature sensing, Oil pressure sensing

Advertising
background image

1-4

DGC-2020 General Information

9400200990 Rev B

1 Second Rating:

2 Aac

5 Aac Current Sensing
Continuous Rating:

0.1 to 5.0 Aac

1 Second Rating:

10 Aac

Voltage Sensing
Configuration:

Line-to-line or line-to-neutral

Range:

12 to 576 V rms, line-to-line

Frequency:

Style selectable, 50/60 Hz or 400 Hz

Frequency Range:

10 to 72 Hz for 50/60 style and 10 to 480 Hz for 400 Hz style

Burden:

1 VA

1 Second Rating:

720 V rms

Generator Sensing Terminals:

41 (A-phase)

39

(B-phase)

37

(C-phase)

35

(Neutral)

Bus Sensing Terminals:

45 (A-phase)

43

(B-phase)

Contact Sensing
Contact sensing inputs include 1 emergency stop input and 16 programmable inputs. The emergency
stop input accepts normally closed, dry contacts. All programmable inputs accept normally open, dry
contacts.

Terminals
Emergency Stop:

46, 47

Programmable

Input 1:

30, 2

Input 2:

29, 2

Input 3:

28, 2

Input 4:

27, 2

Input 5:

26, 2

Input 6:

25, 2

Input 7:

24, 2

Input 8:

23, 2

Input 9:

22, 2

Input 10:

21, 2

Input 11:

20, 2

Input 12:

19, 2

Input 13:

18, 2

Input 14:

17, 2

Input 15:

16, 2

Input 16:

15, 2

Engine System Inputs
∗ Stated accuracies are subject to the accuracy of the senders used.

Fuel Level Sensing
Resistance Range:

33 to 240 Ω nominal

Terminals:

9, 11 (sender common)

Coolant Temperature Sensing
Resistance Range:

62.6 to 637.5 Ω nominal

Terminals:

10, 11 (sender common)

Oil Pressure Sensing
Resistance Range:

34 to 240 Ω nominal

Terminals:

8, 11 (sender common)