Winco DGC-2020 User Manual

Page 180

Advertising
background image

B-22 DGC-2020

Modbus

Communication

9400200990 Rev B

Holding

Register

Parameter Range

Read/Write

Supported

Data

Format

Units

40507

Read Relay Image of both Main
and Aux Output
(Duplicate of 40298)

individual bits
are 0 or 1

R

Main is in lower byte and Aux is in
upper byte.
b0 = Aux Output 1,
b1 = Aux Output 2,
b2 = Aux Output 3,
b3 = Aux Output 4,
b4 = Aux Output 5,
b5 = Aux Output 6,
b6 = Aux Output 7,
b7 = Aux Output 8.
b8 = Master Start Relay,
b9 = Fuel Solenoid Relay,
b10 = PreHeat PreLube Relay,
b11 = Alarm Relay,
b12 = UNASSIGNED,
b13 = Buzzer On,
b14 = EPS Loaded Relay,
b15 = PreAlarm Relay,

40508

Input Contacts States
(Duplicate of 40273)

individual bits
are 0 or 1

R

b0 = coolant level,
b1 = ATS,
b2 = E-stop,
b3 = charger failed,
b4 = aux. input 1,
b5 = aux. input 2,
b6 = aux. input 3,
b7 = aux. input 4.

/* b7 =

aux. input 4. */

40509-604 RESERVED

OVERCURRENT

40605

51 Pick-up – 3-phase

18-118,
90-775

R W

0.18-1.18 Aac for 1A CTs,
0.90-7.75 Aac for 5A CTs

40606

51 Time Dial – 3-phase

0-99,
0-300

R W

0.0-9.9 for 40607=0-15 (inverse),
0.0-30.0s for 40607=16 (fixed)

40607

51 Curve – 3-phase

0-16

R W

0-15 for inverse, 16 for fixed

40608

51 Alarm Config. – 3-phase

0-2

R W

0=None, 1=Pre-Alarm, 2=Alarm

40609

51 Pick-up – 1-phase

18-118,
90-775

R W

0.18-1.18 Aac for 1A CTs,
0.90-7.75 Aac for 5A CTs

40610

51 Time Dial – 1-phase

0-99,
0-300

R W

0.0-9.9 for 40607=0-15 (inverse),
0.0-30.0s for 40607=16 (fixed)

40611

51 Curve – 1-phase

0-16

R W

0-15 for inverse, 16 for fixed

40612

51 Alarm Config. – 1-phase

0-2

R W

0=None, 1=Pre-Alarm, 2=Alarm

PHASE IMBALANCE

40613

47 Pick-up

5-100

R W

Volts AC

40614

47 Time Delay

0-300

R W

0.0-30.0 seconds

40615

47 Alarm Configuration

0-2

R W

0=None, 1=Pre-Alarm, 2=Alarm

UNDERVOLTAGE

40616

27 Pick-up – 3-phase

70-576

R W

Volts AC

40617

27 Time Delay – 3-phase

0-300

R W

0.0-30.0 seconds

40618

27 Inhibit Frequency- 3-ph.

20-400

R W

Hertz

40619

27 Alarm Config. – 3-phase

0-2

R W

0=None, 1=Pre-Alarm, 2=Alarm

40620

27 Pick-up – 1-phase

70-576

R W

Volts AC

40621

27 Time Delay – 1-phase

0-300

R W

0.0-30.0 seconds

40622

27 Inhibit Frequency – 1-ph.

20-400

R W

Hertz

40623

27 Alarm Config. – 1-phase

0-2

R W

0=None, 1=Pre-Alarm, 2=Alarm

OVERVOLTAGE

40624

59 Pick-up – 3-phase

70-576

R W

Volts AC

40625

59 Time Delay – 3-phase

0-300

R W

0.0-30.0 seconds

40626

59 Alarm Config. – 3-phase

0-2

R W

0=None, 1=Pre-Alarm, 2=Alarm

40627

59 Pick-up – 1-phase

70-576

R W

Volts AC

40628

59 Time Delay – 1-phase

0-300

R W

0.0-30.0 seconds

40629

59 Alarm Config. – 1-phase

0-2

R W

0=None, 1=Pre-Alarm, 2=Alarm

Advertising