DGC-2020 Modbus

Communication

B-25

Holding
Register

Parameter Range

Read/Write
Supported

Data
Format

Units

42042

Breaker Close Wait Time

0.1 - 600.0

R W

FP

seconds in

increments of
0.1

42044

Sync Time Delay

0.1 - 0.8

R W

FP

seconds in
increments of
0.1

42046

Sync Fail Time Delay

0.1 - 600.0

R W

FP

seconds in
increments of
0.1

42048

Mains Fail Transfer Enable

0-1

R W

0 = Disabled,
1 = Enabled

42050

Gen Breaker Status

0-1

R

0 = Open,
1 = Closed

42052

Mains Breaker Status

0-1

R

0 = Open,
1 = Closed

42054-248 FUTURE

USE

SYNCHRONIZER BIAS CONTROLS

42250-92 RESERVED

42294-498 FUTURE

USE

42500

AVR Correction Pulse Width

0-999

R W

milliseconds * 100 in increments of 1

42502

AVR Correction Pulse Interval

0-999

R W

milliseconds * 100 in increments of 1

42504

AVR Bias Contact Type

0-1

R W

0 = Continuous,
1 = Proportional

42506 RESERVED

42508

Governor Correction Pulse Width

0-999

R W

milliseconds * 100 in increments of 1

42510

Governor Correction Pulse Interval

0-999

R W

milliseconds * 100 in increments of 1

42512

Governor Bias Contact Type

0-1

R W

0 = Continuous,
1 = Proportional

42514 RESERVED

42516-748 FUTURE

USE

BUS CONDITION DETECTION

42750

Gen Sensing Dead Bus Pickup

0-4800

R W

(Volts / 10) in increments of 10

42752

Gen Sensing Dead Bus Time Delay

1-6000

R W

(milliseconds * 100) in increments of 1

42754 RESERVED

42756

Gen Sensing Stable Undervoltage
Pickup

100-12000

R W

(Volts / 10) in increments of 10

42758

Gen Sensing Stable Undervoltage
Dropout

100-12000

R W

(Volts / 10) in increments of 10

42760

Gen Sensing Stable Overvoltage
Pickup

100-12000

R W

(Volts / 10) in increments of 10

42762

Gen Sensing Stable Overvoltage
Dropout

100-12000

R W

(Volts / 10) in increments of 10

42764

Gen Sensing Stable
Underfrequency Pickup

4600-6400

R W

(Hz / 100) in increments of 5

42766

Gen Sensing Stable
Underfrequency Dropout

4600-6400

R W

(Hz / 100) in increments of 5

42768

Gen Sensing Stable Overfrequency
Pickup

4600-6400

R W

(Hz / 100) in increments of 5

42770

Gen Sensing Stable Overfrequency
Dropout

4600-6400

R W

(Hz / 100) in increments of 5

42772

Gen Sensing Fail Time Delay

1-6000

R W

(milliseconds * 100) in increments of 1

42774

Gen Sensing Stable Time Delay

1-6000

R W

(milliseconds * 100) in increments of 1

42776 RESERVED

42778

Bus Sensing Dead Bus Pickup

0-4800

R W

(Volts / 10) in increments of 10

42780

Bus Sensing Dead Bus Time Delay

1-6000

R W

(milliseconds * 100) in increments of 1

42782 RESERVED

42784

Bus Sensing Stable Undervoltage
Pickup

100-12000

R W

(Volts / 10) in increments of 10

42786

Bus Sensing Stable Undervoltage
Dropout

100-12000

R W

(Volts / 10) in increments of 10

42788

Bus Sensing Stable Overvoltage
Pickup

100-12000

R W

(Volts / 10) in increments of 10

Advertising