DGC-2020 Time Overcurrent Characteristic Curves

9400200990 Rev B

Table A-3 .Time Dial Setting Cross-Reference

Electromechanical Relay Time Dial Setting

0.5 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0

Curve

Equivalent

To

Drawing

Number

Basler Electric Equivalent Time Dial Setting

S, S1

ABB CO-2

99-1369

0.3

0.8

1.7 2.4 3.4 4.2 5.0 5.8 6.7 7.7 8.6 9.7

L, L1

ABB CO-5

99-1370

0.4

0.8

1.5 2.3 3.3 4.2 5.0 6.0 7.0 7.8 8.8 9.9

D

ABB CO-6

99-1371

0.5

1.1

2.0 2.9 3.7 4.5 5.0 5.9 7.2 8.0 8.9 10.1

M

ABB CO-7

99-1369

0.4

0.8

1.7 2.5 3.3 4.3 5.3 6.1 7.0 8.0 9.0 9.8

I, I1

ABB CO-8

99-1373

0.3

0.7

1.5 2.3 3.2 4.0 5.0 5.8 6.8 7.6 8.7 10.0

V, V1

ABB CO-9

99-1374

0.3

0.7

1.4 2.1 3.0 3.9 4.8 5.7 6.7 7.8 8.7 9.6

E, E1

ABB CO-11

99-1375

0.3

0.7

1.5 2.4 3.2 4.2 5.0 5.7 6.6 7.8 8.5 10.3

I2

GE IAC-51

99-1597

0.6

1.0

1.9

2.7

3.7 4.8 5.7 6.8 8.0 9.3 10.6

N/A

V2

GE IAC-53

99-1596

0.4

0.8

1.6

2.4

3.4 4.3 5.1 6.3 7.2 8.4 9.6 N/A

S2

GE IAC-55

99-1595

0.2

1.0

2.0

3.1

4.0 4.9 6.1 7.2 8.1 8.9 9.8 N/A

L2

GE IAC-66

99-1594

0.4

0.9

1.8

2.7

3.9 4.9 6.3 7.2 8.5 9.7 10.9

N/A

E2

GE IAC-77

99-1598

0.5

1.0

1.9

2.7

3.5 4.3 5.2 6.2 7.4 8.2 9.9 N/A