Engine rpm, Engine run time, Maintenance timer – Winco DGC-2020 User Manual

Page 17: Fuel level, Generator protection functions, Overvoltage (59) and undervoltage (27), Underfrequency (81u) and overfrequency (81o), Overcurrent (51) (optional), Phase imbalance (47) (optional), Logic timers

Advertising
background image

9400200990 Rev B

DGC-2020 General Information

1-7

Engine RPM
Metering Range:

0 to 4,500 rpm

Accuracy:

±2% of actual indication or ±2 rpm

Display Resolution:

2 rpm

∗ When engine speed is below 2% of full-scale, reported rpm is 0.

Engine Run Time
Engine run time is retained in nonvolatile memory.
Metering Range:

0 to 99,999 h

Update Interval:

6 min

Accuracy:

±1% of actual indication or ±12 min

Display Resolution:

1/10 hour

Maintenance Timer
Maintenance timer indicates the time remaining until genset service is due. Value is retained in
nonvolatile memory.
Metering Range:

0 to 5,000 h

Update Interval:

6 min

Accuracy:

±1% or actual indication or ±12 min

Display Resolution:

1/10 hour

Fuel Level
Metering Range:

0 to 100%

Accuracy:

±2% (subject to accuracy of sender)

Display Resolution:

1.0%

Generator Protection Functions

Overvoltage (59) and Undervoltage (27)
Pickup Range:

70 to 576 Vac

Pickup Increment:

1 Vac

Inhibit Frequency Range:

20 to 400 Hz (27 function only)

Activation Delay Range:

0 to 30 s

Activation Delay Increment:

0.1 s

Underfrequency (81U) and Overfrequency (81O)
Pickup Range:

45 to 66 Hz (50/60 Hz nominal)

360 to 440 Hz (400 Hz nominal)

Pickup Increment:

0.1 Hz (50/60 Hz nominal)

0.1

Hz

(400

Hz

nominal)

Activation Delay Range:

0 to 30 s

Activation Delay Increment:

0.1 s

Inhibit Voltage Range:

70 to 576 Vac (81U function only)

Overcurrent (51) (Optional)
Pickup Range:

0.18 to 1.18 Aac (1 A current sensing)

0.9 to 7.75 Aac (5 A current sensing)

Time Dial Range:

0 to 30 s (fixed time curve)

0 to 9.9 (inverse curve time multiplier)

Time Dial Increment:

0.1

Inverse Time Curves:

See Appendix A, Time Overcurrent Characteristic Curves

Phase Imbalance (47) (Optional)
Pickup Range:

5 to 100 Vac

Pickup Increment:

1 Vac

Activation Delay Range:

0 to 30 s

Activation Delay Increment:

0.1 s

Logic Timers
Range:

0 to 10 s

Advertising