9400200990 Rev B

DGC-2020 Modbus

Communication

B-21

Holding

Register

Parameter Range

Read/Write

Supported

Data

Format

Units

40490

ECU Param. Status Group 8

R

bits 0-2: % engine torque at point 4
bits 3-5: engine speed at point 5
bits 6-8: % engine torque at point 5
bits 9-11: engine speed at high idle
point 6
bits 12-14: gain (Kp) of endspeed
governor
Bit 15: NOT USED

3-Bit Status Flag Values:
000 for Valid Data
001 for No Comms
010 for Not Sent
011 for Not Supp
100 for Sender Error

40491

ECU Param. Status Group 9

R

bits 0-2: reference engine torque
bits 3-5: max. momentary engine
override speed point 7
bits 6-8: max. momentary engine
override time limit
bits 9-11: requested speed control
range lower limit
bits 12-14: requested speed control
range upper limit
Bit 15: NOT USED

3-Bit Status Flag Values:
000 for Valid Data
001 for No Comms
010 for Not Sent
011 for Not Supp
100 for Sender Error

40492

ECU Param. Status Group 10

R

bits 0-2: requested torque control
range lower limit
bits 3-5: requested torque control
range upper limit
bits 6-8: not used
bits 9-11: not used
bits 12-14: not used
Bit 15: NOT USED

3-Bit Status Flag Values:
000 for Valid Data
001 for No Comms
010 for Not Sent
011 for Not Supp
100 for Sender Error

40493-99 FUTURE

USE

40500

DGC-2020 product series identifier

2020

R


40501

Firmware Part Number - 2nd most
significant digit. NOTE: The most
significant digit is always 9, but is
not mapped.

0 - 9

R

40502

Firmware Part Number - 3rd-6th
most significant digits

0000 - 9999

R

40503

Firmware Part Number - four least
significant digits

0000 - 9999

R

40504 LED

Status

individual bits
are 0 or 1

R

Bits indicate status of LED’s:
b0 = RUN
b1 = OFF
b2 = AUTO
b3 = ALARM
b4 = LOAD
b5 = NOT IN AUTO