4-15

Horn

An output contact configured (through programmable logic) to energize a horn

M

can be enabled and

disabled through BESTCOMSPlus or at the DGC-2020 front panel.

Single-Phase Override

The DGC-2020 will switch to single-phase voltage sensing

N

when a contact input (programmed as a

single-phase override input) is received. Either A-to-B or A-to-C sensing can be selected.

Fuel Level Function

This setting

O

allows the selection of four fuel types: Fuel Lvl, Natural Gas, Liquid Propane, or Disabled.

Selecting a fuel type other than Fuel Lvl will disable any fuel level indication, alarm, and pre-alarm and
disable the Fuel Level value on the Engine screen of the Metering Explorer in BESTCOMSPlus.

BESTCOMSPlus system settings (DGC-2020, System Parameters, System Settings) are illustrated in
Figure 4-15.

Figure 4-15. BESTCOMSPlus System Settings

A

Generator Connection: Delta, Wye, 1-Phase A-B, 1-Phase A-C, or 4-Wire Delta.

B

Genset kW Rating: Adjustable from 5 to 9,999 kW in 1 kW increments.

C

Rated Volts: Adjustable from 1 to 999 Vac in 1 Vac increments.

D

Speed Signal Source: MPU, Gen Freq, or MPU_Gen Freq.

E

Rated Frequency: 50/60 or 400 Hz.

F

Rated Engine RPM: Adjustable from 750 to 3,600 rpm in 1 rpm increments.

G

Number Fly Wheel Teeth: Adjustable from 50 to 500 in increments of 1.

H

No Load Cool Down Time: Adjustable from 0 to 60 minutes in 1 minute increments.

I

EPS Current Threshold: Adjustable from 3 to 10% of the CT primary rating in 1% increments.

J

System Units: Either English or Metric.

K

Battery Volts: Either 12 or 24 Vdc.

L

NFPA Level: 0 disables NFPA compliance, 1 enables Level 1 NFPA compliance, 2 enables Level 2.

M

Horn: either Enable or Disable.

N

1 Phase Override Sensing: Either phases A-B or phases A-C.

O

Fuel Level Function: Disable, Fuel Lvl, Natural Gas, or Liquid Propane.

Crank Settings

The DGC-2020 can be programmed for either cycle or continuous engine cranking

A

. Cycle cranking

provides multiple engine starting attempts

B

. Each starting attempt consists of a fixed interval of engine

cranking

C

followed by a rest interval of the same duration. Continuous cranking

D

provides a single,

extended engine-starting attempt.

The DGC-2020 uses the engine speed signal (supplied by a magnetic pickup (MPU) or the generator
frequency) and the Crank Disconnect Limit setting

E

to detect engine startup (and determine when engine

cranking can be stopped). The Crank Disconnect Limit setting is expressed as a percentage of the
nominal engine speed.