Generator frequency, Apparent power, Power factor – Winco DGC-2020 User Manual

Page 16: Real power, Oil pressure, Coolant temperature, Battery voltage

Advertising
background image

1-6

DGC-2020 General Information

9400200990 Rev B

CT Primary Range:

1 to 5,000 Aac in primary increments of 1 Aac

Accuracy:

±1.0% of programmed rated current or ±2 Aac

Display Resolution:

1 Aac

∗ Current metering indicates 0 A when generator current is below 2% of the full-scale rating.

Generator Frequency
Generator frequency is sensed through the generator voltage input.
Metering Range:

10 to 72 Hz (50/60 Hz)

10 to 480 (400 Hz)

Accuracy:

±0.25% or 0.05 Hz

Display Resolution:

0.1 Hz

Apparent Power
Indicates total kVA and individual line kVA (4-wire, line-to-neutral or 3-wire, line-to-line).
Measurement/Calculation Methods

Total:

kVA = (V

L-L

× I

L

Ч√3) ч 1000

4-Wire, Line-to-Neutral:

kVA calculated with respect to neutral

3-Wire, Line-to-Line:

A-phase kVA = V

AB

× I

A

ч 1000 ч √3

B-phase

kVA

=

V

BC

× I

B

ч 1000 ч √3

C-phase kVA = V

CA

× I

C

ч 1000 ч √3

Accuracy:

±3% or the full-scale indication or ±2 kVA ∗†

∗ kVA metering indicates 0 kVA when the generator kVA is below 2% of the full-scale rating.
† Applies when temperature is between -40

°C to +70°C.

Power Factor
Metering Range:

0.2 leading to 0.2 lagging

Calculation Method:

PF = P (3-phase average)

÷ S (3-phase average)

Accuracy:

±0.02 ∗

∗ Applies when temperature is between -40°C to +70°C.

Real Power
Indicates total kW and individual line kW (4-wire, line-to-neutral or 3-wire line-to-line)
Measurement/Calculation Methods
Total:

PF

× Total kVA

4-Wire, Line-to-Neutral:

kW calculated with respect to neutral

3-Wire, Line-to-Line:

A-phase kW = V

AB

× I

A

× PF ч 1000 ч √3

B-phase

kVA

=

V

BC

× I

B

× PF ч 1000 ч √3

C-phase kVA = V

CA

× I

C

× PF ч 1000 ч √3

Accuracy:

±3% of the full-scale indication or ±2 kW ∗†

∗ kW metering indicates 0 kW when the generator kW is below 2% of the full-scale rating.
† Applies when temperature is between -40

°C to +70°C.

Oil Pressure
Metering Range:

0 to 145 psi or 0 to 1,000 kPa

Accuracy:

±3% of actual indication or ±2 psi or ±12 kPa (subject to accuracy of
sender)

Display Resolution:

1 psi or 1 kPa

Coolant Temperature
Metering Range:

–40 to 410

°F or –40 to 210°C

Accuracy:

±3% or actual indication or ±2° (subject to accuracy of sender)

Battery Voltage
Metering Range:

6 to 32 Vdc

Accuracy:

±3% of actual indication or ±0.2 Vdc

Display Resolution:

0.1 Vdc