Programmable senders, Bestlogic+ programmable logic, Bestlogic+ programmable logic -32 – Winco DGC-2020 User Manual

Page 82

Advertising
background image

4-32

DGC-2020 BESTCOMSPlus Software

9400200990 Rev B

PROGRAMMABLE SENDERS

The sender inputs of the DGC-2020 can be customized to obtain maximum accuracy from the coolant
temperature, oil pressure, and fuel level senders.

The characteristic curve of each sender input can be configured with up to 11 points

A

. Each point can be

assigned a resistance input value and a corresponding temperature (coolant temperature sender),
pressure (oil pressure sender), or percentage (fuel level sender) value. A sender slope setting

B

automatically orders the values in the resistance column according to whether the sender requires a
negative or positive slope. Sender curve points are automatically plotted on a curve

C

in BESTCOMSPlus,

which can be printed

D

.

Sender curve points configured in BESTCOMSPlus can be saved in the configuration file

E

. The data for

all three senders is automatically saved with the DGC-2020 configuration file.

Any changes made in BESTCOMSPlus to the sender points, can be reverted to the factory-default
values

F

. A new settings file can also be created

G

.

BESTCOMSPlus programmable sender settings (DGC-2020, Programmable Senders, Coolant
Temperature, Oil Pressure, or Percent Fuel Level) are illustrated in Figure 4-30. (The contents and layout
of each BESTCOMSPlus programmable sender screen is identical; only the coolant temperature sender
screen is illustrated here.)

Figure 4-30. BESTCOMSPlus Programmable Senders Settings

A

Sender Points: Accepts up to 11 user-defined sender resistance points.

B

Sender Slope: Positive or Negative causes sender points to be sorted and displayed accordingly.

C

Sender Point Curve: Automatic plot of sender points data.

D

Print This Graph: Click to print sender point curve.

E

Save Cool. Data File: Click to save file containing sender point data.

F

Load Cool. Settings File: Click to clear all user-defined sender data and revert to the factory-default

values.

G

Create Cool. Settings File: Click to create a new settings file by entering sender point data.

BESTlogic+ PROGRAMMABLE LOGIC

BESTlogic+ Programmable Logic is used to set all logic functions in the DGC-2020. For detailed
information on using BESTlogic+, refer to Section 5, BESTlogic+ Programmable Logic.

Advertising