9400200990 Rev B

DGC-2020 BESTCOMSPlus Software

4-13

Figure 4-13. BESTCOMSPlus Modem Setup

A

Dial Out Number: Accepts a telephone number of up to 16 characters.

B

Pager ID: Accepts a pager identification number of up to 16 characters.

C

Modem Dialout Conditions: Check boxes to select conditions that will initiate a dial-out message.

D

Pager Coms Data Format: 7 bit – Even Parity or 8 bit – No Parity.

E

Pager Buffer Limit: Adjustable from 80 to 200 characters in increments of 40.

F

Modem Offline Delay: Adjustable from 1 to 240 min in 1 min increments.

G

Inter Dialout Activation Delay: A delay of 15, 30, 60, or 120 s may be selected.

H

Rings for Modem Answer: Adjustable from 1 to 9 in increments of 1.

RS-485 (Optional)

DGC-2020 controllers with the optional RS-485 communication port (style number xxxRxxxxx) can be
monitored and controlled via a polled network using the Modbus protocol. Adjustable RS-485 port settings
include the baud rate

A

, parity

B

, and port address

C

. Fixed RS-485 port settings include the number of data

bits (8) and stop bits (1).

Modbus register values for the DGC-2020 are listed and defined in Appendix B, Modbus Communication.

BESTCOMSPlus RS-485 port settings are illustrated in Figure 4-14.

Figure 4-14. BESTCOMSPlus RS-485 Port Settings

A

Baud Rate: A value of 1200, 2400, 4800, or 9600 may be selected.

B

Parity: No Parity, Odd Parity, or Even Parity.

C

Modbus Address: A value of 1 to 247 may be entered in increments of 1.