Programmable inputs, Configurable inputs, Are illustrated in figure 4-17 – Winco DGC-2020 User Manual

Page 67

Advertising
background image

9400200990 Rev B

DGC-2020 BESTCOMSPlus Software

4-17

Figure 4-17. BESTCOMSPlus Sensing Transformers Parameters

A

Gen PT Primary Volts: Adjustable from 1 to 9999 Vac in 1 Vac increments.

B

Gen PT Secondary Volts: Adjustable from 1 to 480 Vac in 1 Vac increments.

C

Gen CT Primary Amps: Adjustable from 1 to 5,000 Aac in 1 Aac increments.

D

Bus PT Primary Volts: Adjustable from 1 to 9999 Vac in 1 Vac increments.

E

Bus PT Secondary Volts: Adjustable from 1 to 480 Vac in 1 Vac increments.

PROGRAMMABLE INPUTS

DGC-2020 contact inputs can be assigned to trigger various functions and, when triggered, annunciate an
alarm or pre-alarm. A user-assigned label can be assigned to each input to make identification easier.
The description of these settings is organized as follows:
• Configurable

inputs

• Programmable

Functions

Configurable Inputs

Each of the 16 contact inputs can be independently configured to annunciate an alarm or pre-alarm

A

when the input senses a contact closure. A user-adjustable time delay

B

can be set to delay recognition of

a contact input. By default, all inputs are configured so that they do not trigger an alarm or pre-alarm.

To make identifying the contact inputs easier, a user-assigned name

C

can be given to each input.

BESTCOMSPlus settings for the configurable contact inputs (DGC-2020, Programmable Inputs,
Configurable Inputs) are illustrated in Figure 4-18.