Programmable outputs, Configurable outputs, Figure 4-19 – Winco DGC-2020 User Manual

Page 69

Advertising
background image

9400200990 Rev B

DGC-2020 BESTCOMSPlus Software

4-19

Figure 4-19. BESTCOMSPlus Settings for Programmable Functions

A

Auto Transfer Switch Input: None, Input 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, or 16.

B

Battle Override: None, Input 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, or 16.

C

Low Line Override: None, Input 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, or 16.

D

Grounded Delta Override: None, Input 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, or 16.

E

Single Phase Override: None, Input 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, or 16.

F

Single Phase AC Override: None, Input 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, or 16.

G

Battery Charger Fail: Select Input (None, 1-16), Alarm Configuration (None, Alarm, Prealarm), and

Activation Delay (s) (0 to 300 in increments of 1).

H

Low Coolant Level: Select Input (None, 1-16), Alarm Configuration (None, Alarm, Prealarm), and

Activation Delay (s) (0 to 300 in increments of 1).

I

Fuel Leak Detect: Select Input (None, 1-16), Alarm Configuration (None, Alarm, Prealarm), and

Activation Delay (s) (0 to 300 in increments of 1).

PROGRAMMABLE OUTPUTS

DGC-2020 output contacts include four user-programmable output contacts if the style number is
xxAxxxxxx. If the style number is xxBxxxxxx, twelve output contacts are provided.

Configurable Outputs

To make identifying the output contacts easier, each of the output contacts can be given a user-assigned
name

A

.

BESTCOMSPlus settings for the configurable output contacts (DGC-2020, Programmable Outputs,
Configurable Outputs) are illustrated in Figure 4-20.