DGC-2020 Modbus

Communication

B-9

Table B-3. Legacy Parameter Table

Holding

Register

Parameter Range

Read/Write

Supported

Data

Format

Units

40001-18 RESERVED

PARAMETER SETTINGS

40019 Emergency

Stop

0-1

W

0 =Off
1 =Stop

40020

Remote Start / Stop

0-1

W

0 =Stop
1 =Start

40021-22 RESERVED

SYSTEM PARAMETERS

40023

Default Generator Connection

0-2

R W

0=3ph L-L
1=3ph L-N
2=1ph A-B

40024

NFPA Level

0-2

R W

0=Off
1=Level 1
2=Level 2

40025 RESERVED

40026

Rated Engine RPM

750-3600

R W

RPM

40027

Number Flywheel Teeth

50-500

R W

40028

Genset KW Rating

25-9999

R W

KWatt

40029

No Load Cool Down Time

0-60

R W

Minutes

GENERATOR PT PRIMARY

40030

Voltage(a)

1-15000

R W

DP

VoltsAC x10000

40031 Voltage(b)

R

W DP

VoltsAC

GENERATOR PT SECONDARY

40032

Voltage

1-480

R W

VoltsAC

GENERATOR CT PRIMARY

40033

Current

1-5000

R W

AmpsAC

LOW FUEL ALARM

40034 Enable

0-1

R

W

0 =Off
1 =On

40035

Threshold

2-50

R W

% Full Tank

LOW FUEL PRE-ALARM

40036 Enable

0-1

R

W

0 =Off
1 =On

40037

Threshold

10-100

R W

% Full Tank

LOW COOLANT TEMP PRE-ALARM

40038 Enable

0-1

R

W

0 =Off
1 =On

40039

Threshold

40-100

R W

Degrees F

BATTERY OVERVOLTAGE PRE-ALARM

40040 Enable

0-1

R

W

0 =Off
1 =On

40041 RESERVED

MAINTENANCE INTERVAL PRE-ALARM

40042 Enable

0-1

R

W

0 =Off
1 =On

40043 Threshold

0-5000

R

W

Hours

ENGINE KW OVERLOAD PRE-ALARM

40044 Enable

0-1

R

W

0 =Off
1 =On

40045

Threshold

95-140

R W

% of Rated

HIGH COOLANT TEMP PRE-ALARM

40046 Enable

0-1

R

W

0 =Off
1 =On

40047

Threshold

100-280

R W

Degrees F

LOW OIL PRESSURE PRE-ALARM

40048 Enable

0-1

R

W

0 =Off
1 =On