DGC-2020 Modbus

Communication

B-23

Holding

Register

Parameter Range

Read/Write

Supported

Data

Format

Units

UNDERFREQUENCY

40630 81U

Pick-up

450-550,
550-650,
3600-4400

R W

45.0-55.0 Hz for 50-Hz config.,
55.0-65.0 Hz for 60-Hz config.,
360.0-440.0 Hz for 400-Hz unit

40631

81U Time Delay

0-300

R W

0.0-30.0 seconds

40632

81U Inhibit Voltage

70-576

R W

Volts AC

40633

81U Alarm Configuration

0-2

R W

0=None, 1=Pre-Alarm, 2=Alarm

OVERFREQUENCY

40634 81O

Pick-up

450-550,
550-650,
3600-4400

R W

45.0-55.0 Hz for 50-Hz config.,
55.0-65.0 Hz for 60-Hz config.,
360.0-440.0 Hz for 400-Hz unit

40635

81O Time Delay

0-300

R W

0.0-30.0 seconds

40636 81O

Alarm

Configuration

0-2

R

W

0=None, 1=Pre-Alarm, 2=Alarm

GENERATOR PROTECTION STATUS

40637

Gen Protection Status (upper 16
bits)

0-65535 R

b16-b31

UNASSIGNED

40638

Gen Protection Status (lower 16
bits)

0-65535 R

b0 = overvoltage trip,
b1 = undervoltage trip,
b2 = overfrequency trip,
b3 = underfrequency trip,
b4 = overcurrent trip,
b5 = phase imbalance trip,
b6-b15 UNASSIGNED

40639

Gen Protection Pre-Alarms (upper
16 bits)

0-65535 R

b16-b31

UNASSIGNED

40640

Gen Protection Pre-Alarms (lower
16 bits)

0-65535 R

b0 = overvoltage pre-alarm,
b1 = undervoltage pre-alarm,
b2 = overfrequency pre-alarm,
b3 = underfrequency pre-alarm,
b4 = overcurrent pre-alarm,
b5 = phase imbalance pre-alarm,
b6-b15 UNASSIGNED

40641

Gen Protection Alarms (upper 16
bits)

0-65535 R

b16-b31

UNASSIGNED

40642

Gen Protection Alarms (lower 16
bits)

0-65535 R

b0 = overvoltage alarm,
b1 = undervoltage alarm,
b2 = overfrequency alarm,
b3 = underfrequencyalarm,
b4 = overcurrent alarm,
b5 = phase imbalance alarm,
b6-b15 UNASSIGNED

REAL TIME CLOCK

40700 Hours

0-23

R

W

40701 Minutes

0-59

R

W

40702 Seconds

0-59

R

W

40703 Month

1-12

R

W

40704 Day

1-31

R

W

40705 Year

R

W

40706

Daylight Savings Time Enable

0-1

R W

0 = Off
1 = On

40707-57 RESERVED

ROLLING EVENT LOG ACCESS

40758

ECU Control Output Select

0-1

R W

0 = fuel solenoid relay,
1 = pre-start relay

40759

ECU Pulsing Enable

0-1

R W

0 = pulsing is enabled,
1 = pulsing is disabled