Breaker management, Breaker hardware – Winco DGC-2020 User Manual

Page 78

Advertising
background image

4-28

DGC-2020 BESTCOMSPlus Software

9400200990 Rev B

settings. For example, if a scale factor contact input is received by the DGC-2020 and the scale factor
setting is 2.000, the pickup setting will be doubled (2.000

× PU).

The graph can be set

G

to display the 1 Phase or 3 Phase curve as determined by the settings on the left

side of the chart.

BESTCOMSPlus overcurrent protection settings (DGC-2020, Generator Protection, Overcurrent) are
illustrated in Figure 4-26.

Figure 4-26. BESTCOMSPlus Overcurrent Protection Settings

A

Pickup: Adjustable from 0.9 to 7.75 Aac for 5 Aac current sensing (style number 5xxxxxxxx) or 0.18 to

1.18 Aac for 1 Aac current sensing (style number 1xxxxxxxx).

B

Alarm Configuration: None, Alarm, or Prealarm

C

Time Dial: Adjustable from 0 to 30 s for F (fixed) curve, 0 to 9.9 for all other curve selections.

D

Curve: A, B, C, D, E1, E2, F, G, I1, I2, L1, L2, M, S1, S2, V1, or V2.

E

Overcurrent Pickup Curve.

F

Low Line Scale Factor: Adjustable from 0 to 3.000 in 0.001 increments.

G

Display: 1 Phase or 3 Phase.

BREAKER MANAGEMENT

DGC-2020 breaker management features include the control of two, continuous- or pulse-controlled
breakers, load transfer upon detection of a mains failure, two modes of automatic genset synchronization,
and settings for stable or dead bus detection.

The description of breaker management is organized as follows:
• Breaker

Hardware

• Bus Condition Detection

• Synchronizer

Breaker Hardware

By default, one (generator) breaker is enabled

A

for control and monitoring by the DGC-2020. In

applications requiring control of a generator breaker and mains breaker, a second (mains) breaker can be
enabled

B

and configured.

When two breakers are configured (enabled), the DGC-2020 can be enabled to automatically transfer
load power from the mains to the genset during a mains failure

C

. This feature also enables the DGC-2020