DGC-2020 General Information

1-9

Type Tests
Shock and Vibration:

EN60068-2-6

Dielectric Strength:

IEC 255-5

Impulse: EN60664-1
Transients: EN61000-4-4
Static Discharge:

EN61000-4-2

Shock
15 G in 3 perpendicular planes

Vibration
Swept over the following ranges for 12 sweeps in each of three mutually perpendicular planes with each
15-minute sweep consisting of the following:
5 to 29 to 5 Hz:

1.5 G peak for 5 min.

29 to 52 to 29 Hz:

0.036” DECS-A for 2.5 min.

52 to 500 to 52 Hz:

5 G peak for 7.5 min.

Radio Interference
Type tested using a 5 W, hand-held transceiver operating at random frequencies centered around 144
and 440 MHz with the antenna located within 150 mm (6”) of the device in both vertical and horizontal
planes.

HALT (Highly Accelerated Life Testing)
Halt Testing is a method used by many high quality manufacturers to prove that their products will provide
the user with many years of reliable service. Halt testing is a method to subject the device to extremes in
temperature, shock, and vibration to simulate years of operation, but in a much shorter period span. Halt
testing allows Basler to evaluate all possible design elements that will add to the increase in the life of this
device. As an example of some of the extreme testing conditions, the DGC-2020 was subjected
to Temperature Tests (Tested over a temperature range of -100

°C to +115°C),

Vibration Tests (Swept

over a frequency of 5 to 50 G at +20

°C), and Temperature/Vibration Tests (Tested at 40 G over a

temperature range of -80

°C to +90°C). Combined temperature and vibration testing at these extremes

proves that the DGC-2020 design is the most rugged device of its type. Please note that the vibration and
temperature extremes noted in this paragraph are specific to HALT testing and do not reflect
recommended operation level. These operational ratings are included in Section 1 of this manual.

Ignition System
Tested in closed proximity to an unshielded, unsuppressed Altronic DISN 800 Ignition System.

Environment
Temperature

Operating:

–40 to 70

°C (–40 to 158°F)∗

Storage:

–40 to 85

°C (–40 to 185°F)

Humidity: IEC

68-2-38

Salt Fog:

ASTM B 17-73, IEC 68-2-11

Ingress Protection:

IEC IP54 for front panel

∗ Display operation is maintained at -40°C when used with an optional LCD heater. Refer to Figure 1-1,
DGC-2020 Style Chart

for ordering information. Display operation is maintained at -20

°C when the

optional LCD heater is not used.

Agency Approvals

UL/CSA Approvals
“cURus” approved to UL 508 R and CSA C22.2 No.14