Frequency correction, Voltage correction, Synchronization failure – Winco DGC-2020 User Manual

Page 81

Advertising
background image

9400200990 Rev B

DGC-2020 BESTCOMSPlus Software

4-31

Frequency Correction

Generator frequency correction is defined by the slip frequency setting and further refined by the breaker
closing angle setting. The slip frequency setting

E

establishes the maximum allowable deviation of the

generator speed (frequency) from the bus frequency. To minimize the impact on the bus during
synchronization, the Fgen>Fbus setting

F

can be enabled to force the generator frequency to exceed the

bus frequency at the moment of breaker closure. If this is the case, the DGC-2020 will drive the generator
frequency higher than the bus frequency before closing the breaker. The breaker closing angle setting

G

defines the maximum allowable phase angle difference between the generator and the bus. For breaker
closure to be considered, the slip angle must remain below this setting for the duration of the sync
activation delay setting

H

.

Voltage Correction

Generator voltage correction is defined by the regulation offset setting

I

. This setting, expressed as a

percentage of the bus voltage, determines the band of generator voltage surrounding the bus voltage
when breaker closure will be considered. If the Vgen>Vbus setting

J

is enabled, the DGC-2020 will drive

the generator voltage to be greater than the bus voltage by an amount equal to the regulation offset
setting divided by two.

Synchronization Failure

The maximum desired duration for synchronizing to take place is established by the sync fail activation
delay setting

K

. If synchronization (breaker closure) fails to occur within this time setting, generator

synchronization will be aborted and a failure will be annunciated. Note that if either bus goes unstable, the
synchronizer timers are reset.

Figure 4-29. BESTCOMSPlus Synchronizer Settings

A

Sync Type: Phase Lock Loop or Anticipatory.

B

Contact Type: Continuous or Proportional.

C

Correction Pulse Width: Adjustable from 0 to 99.9 s in 0.1 s increments.

D

Correction Pulse Interval: Adjustable from 0 to 99.9 s in 0.1 s increments.

E

Slip Frequency: Adjustable from 0.05 to 0.5 Hz in 0.05 Hz increments.

F

Fgen>Fbus: Enable or Disable.

G

Breaker Closing Angle: Adjustable from 3 to 20

° in 1 ° increments.

H

Sync Activation Delay: Adjustable from 0.1 to 0.8 seconds in 0.1s increments.

I

Regulation Offset: Adjustable from 2 to 15% of nominal generator voltage in 0.5% increments.

J

Vgen>Vbus: Enable or Disable.

K

Sync Fail Activation Delay: Adjustable from 0.1 to 600 in 0.1 s increments.

NOTE

If the generator frequency is 400 Hz, the settings on the Synchronizer screen do
NOT apply. In this case, BESTCOMSPlus will not allow these settings to be
changed.

Advertising