Current parameter table – Winco DGC-2020 User Manual

Page 182

Advertising
background image

B-24 DGC-2020

Modbus

Communication

9400200990 Rev B

Holding

Register

Parameter Range

Read/Write

Supported

Data

Format

Units

40760 MDEC

Alarms

0-65535

R

b0 = High Charge Air Temp,
b1 = High Oil Temp,
b2 = High Coolant Temp,
b3 = Low Aftercooler Level,
b4 = Low Fuel Delivery Press,
b5 = Low Oil Press,
b6 = Overspeed,
b7 = Combined Red,
b8-b15 UNASSIGNED

40761 MDEC

Pre-alarms

0-65535

R

b0 = High ECU Temp,
b1 = High Oil Temp,
b2 = High Intercooler Temp,
b3 = High Charge Air Temp,
b4 = High Coolant Temp,
b5 = Shutdown Override,
b6 = High Fuel Rail Press,
b7 = Low Fuel Rail Press,
b8 = Low Coolant Level,
b9 = Low Charge Air Pressure,
b10 = Low Fuel Deliv Pressure,
b11 = Low Oil Pressure,
b12 = Combined Yellow,
b13-b15 UNASSIGNED

Current Parameter Table

The DGC-2020 maps all non-legacy parameters into the Holding Register address space (42000 and
above). Query address N will access the Holding Register N+1. Data Format is Long Integer type data
unless identified otherwise in the Data Format column. See Table B-4.

Table B-4. Current Parameter Table

Holding
Register

Parameter Range

Read/Write
Supported

Data
Format

Units

BREAKER MANAGEMENT

42000

Gen Breaker Configured

0-1

R

0 = NOT Configured,
1 = Configured

42002

Gen Breaker Open Pulse Time

1-80

R W

milliseconds * 10

42004

Gen Breaker Close Pulse Time

1-80

R W

milliseconds * 10

42006

Gen Breaker Contact Type

0-1

R W

0 = Pulse,
1 = Continuous

42008

Gen Breaker Close Time

0-800

R W

milliseconds in increments of 5

42010 RESERVED

42012

Mains Breaker Configured

0-1

R W

0 = NOT Configured,
1 = Configured

42014

Mains Breaker Open Pulse Time

1-80

R W

milliseconds * 10

42016

Mains Breaker Close Pulse Time

1-80

R W

milliseconds * 10

42018

Mains Breaker Ouput Continuous

0-1

R W

0 = Pulse,
1 = Continuous

42020

Mains Breaker Close Time

0-800

R W

milliseconds in increments of 5

42022 RESERVED

42024 Synchronizer

Type

1-2

R

W

1 = Anticipatory,
2 = Phase Lock Loop

42026 RESERVED

42028

Slip Frequency

5-50

R W

(milliseconds * 10) in increments of 5

42030

Breaker Closing Angle

30-200

R W

Degrees / 10 in increments of 10

42032

Regulation Offset

20-150

R W

(% / 10) in increments of 5

42034

Vgen > Vbus

0-1

R W

0 = Disable
1 = Enable

42036

Fgen > Fbus

0-1

R W

0 = Disable
1 = Enable

42038-40 RESERVED