Winco DGC-2020 User Manual

Page 184

Advertising
background image

B-26 DGC-2020

Modbus

Communication

9400200990 Rev B

Holding
Register

Parameter Range

Read/Write
Supported

Data
Format

Units

42790

Bus Sensing Stable Overvoltage
Dropout

100-12000

R W

(Volts / 10) in increments of 10

42792

Bus Sensing Stable
Underfrequency Pickup

4600-6400

R W

(Hz / 100) in increments of 5

42794

Bus Sensing Stable
Underfrequency Dropout

4600-6400

R W

(Hz / 100) in increments of 5

42796

Bus Sensing Stable Overfrequency
Pickup

4600-6400

R W

(Hz / 100) in increments of 5

42798

Bus Sensing Stable Overfrequency
Dropout

4600-6400

R W

(Hz / 100) in increments of 5

42800

Bus Sensing Fail Time Delay

1-6000

R W

(milliseconds * 100) in increments of 1

42802

Bus Sensing Stable Time Delay

1-6000

R W

(milliseconds * 100) in increments of 1

42804 RESERVED

42806-3432 FUTURE

USE

SENDERS

43434

Coolant Temperature Sender Fail
Configuration Type

-1, 0, 1

R W

0 = None
1 = Alarm
2 = Pre-Alarm

43436

Coolant Temperature Sender Fail
Activation Delay

50-300

R W

Minutes in increments of 5

43438

Oil Pressure Sender Fail
Configuration Type

-1, 0, 1

R W

0 = None
1 = Alarm
2 = Pre-Alarm

43440

Oil Pressure Sender Fail Activation
Delay

0-300

R W

Seconds in increments of 1

43442

Fuel Level Sender Fail
Configuration Type

-1, 0, 1

R W

0 = None
1 = Alarm
2 = Pre-Alarm

43444

Fuel Level Sender Fail Activation
Delay

0-300

R W

Seconds in increments of 1

43446

Voltage Sensing Fail Configuration
Type

-1, 0, 1

R W

0 = None
1 = Alarm
2 = Pre-Alarm

43448

Voltage Sensing Fail Activation
Delay

0-300

R W

Seconds in increments of 1

43450-498 FUTURE

USE

SYSTEM CONFIGURATION AND STATUS

43500

Rated Volts

1-999

R W

Volts in increments of 1

43502

Pre-Start Contact Config

0-1

R W

0 = Open After Disconnect
1 = Closed While Running

43504

System Units

0-1

R W

0 = English
1 = Metric

43506

Battery Volts

0-1

R W

0 = 12V
1 = 24V

43508

Off Mode Status

0-1

R

0 = Disable
1 = Enable

43510

Run Mode Status

0-1

R

0 = Disable
1 = Enable

43512

Auto Mode Status

0-1

R

0 = Disable
1 = Enable

43514

Virtual Input 1 Status

0-1

R

0 = Disable
1 = Enable

43516

Virtual Input 2 Status

0-1

R

0 = Disable
1 = Enable

43518

Virtual Input 3 Status

0-1

R

0 = Disable
1 = Enable

43520

Virtual Input 4 Status

0-1

R

0 = Disable
1 = Enable

43522-748 FUTURE

USE

CONTROL

43750

Emergency Stop

0-1

R W

A value of 1 will invoke the Emergency

Stop