Holding
Register

Parameter Range

Read/Write
Supported

Data
Format

Units

44308 Overfrequency

Pickup

450-550 50Hz
540-660 60Hz
3600-4400
400Hz

R W

(Hz / 10) in increments of 1

44310

Overfrequency Activation Delay

0-300

R W

(Seconds / 10) in increments of 1

44312

Overfrequency Alarm Configuration

0-2

R W

0 = None
1 = Alarm
2 = Pre-Alarm

44314

Overcurrent Low Line Scale Factor

0.000 - 3.000

R W

FP

In increments of
0.001

44316

Overvoltage Low Line Scale Factor

0.000 - 3.000

R W

FP

In increments of
0.001

44318

Undervoltage Low Line Scale
Factor

0.000 - 3.000

R W

FP

In increments of
0.001

44320-498 FUTURE

USE

ALARMS

44500

High Coolant Temp Alarm Enable

0-1

R W

0 = Disable
1 = Enable

44502

High Coolant Temp Alarm
Threshold

100-280

R W

°F in increments of 1

44504

Metric High Coolant Temp Alarm
Threshold

37-137

R W

°C in increments of 1

44506

High Coolant Temp Alarm
Activation Delay

50-150

RW

Seconds in increments of 1

44508

Low Oil Press. Alarm Enable

0-1

R W

0 = Disable
1 = Enable

44510

Low Oil Press. Alarm Threshold

3-150

R W

psi in increments of 1

44512

Metric Low Oil Press. Alarm
Threshold

25-1030

R W

kPa in increments of 1

44514

Low Oil Press. Alarm Arming Delay

5-15

R W

Seconds in increments of 1

44516

Overspeed Alarm Enable

0-1

R W

0 = Disable
1 = Enable

44518

Overspeed Alarm Threshold

105-140

R W

% in increments of 1

44520

Overspeed Alarm Activation Delay

0-500

R W

Milliseconds in increments of 1

44522

Low Fuel Level Alarm Enable

0-1

R W

0 = Disable
1 = Enable

44524

Low Fuel Level Alarm Threshold

0-100

R W

% in increments of 1

44526

Low Fuel Level Alarm Activation
Delay

0-30

R W

Seconds in increments of 1

44528

High Coolant Temp Pre-Alarm
Enable

0-1 R

W

0 = Disable
1 = Enable

44530

High Coolant Temp Pre-Alarm
Threshold

100-280

R W

°F in increments of 1

44532

Metric High Coolant Temp Pre-
Alarm Threshold

37-137

R W

°C in increments of 1

44534

Low Coolant Temp Pre-Alarm
Enable

0-1 R

W

0 = Disable
1 = Enable

44536

Low Coolant Temp Pre-Alarm
Threshold

50-100

R W

°F in increments of 1

44538

Metric Low Coolant Temp Pre-
Alarm Threshold

10-37

R W

°C in increments of 1

44540

High Fuel Level Pre-Alarm
Threshold

0-100

R W

% in increments of 1

44542

High Fuel Level Pre-Alarm Enable

0-1

R W

0 = Disable
1 = Enable

44544

High Fuel Level Pre-Alarm
Activation Delay

0-30

R W

Seconds In increments of 1

44546

Low Fuel Level Pre-Alarm Enable

0-1

R W

0 = Disable
1 = Enable

44548

Low Fuel Level Pre-Alarm
Threshold

10-100

R W

% in increments of 1

44550

Low Battery Pre-Alarm Enable

0-1

R W

0 = Disable
1 = Enable

Advertising