DGC-2020 Time Overcurrent Characteristic Curves

A-3

Table A-2. Characteristic Curve Cross-Reference

Curve Curve

Name

Drawing No.

Similar To

S1

S, S1, Short Inverse

99-1369

ABB CO-2

S2

S2, Short Inverse

99-1595

GE IAC-55

L1

L, L1, Long Inverse

99-1370

ABB CO-5

L2

L2, Long Inverse

99-1594

GE IAC-66

D

D, Definite Time

99-1371

ABB CO-6

M

M, Moderately Inverse

99-1372

ABB CO-7

I1

I, I1, Inverse Time

99-1373

ABB CO-8

I2

I2, Inverse Time

99-1597

GE IAC-51

V1

V, V1, Very Inverse

99-1374

ABB CO-9

V2

V2, Very Inverse

99-1596

GE IAC-53

E1

E, E1, Extremely Inverse

99-1375

ABB CO-11

E2

E2, Extremely Inverse

99-1598

GE IAC-77

A

A, Standard Inverse

99-1621

BS, IEC Standard Inverse

B

B, Very Inverse (I

2

t)

99-1376

BS, IEC Very Inverse (I

2

t)

C

C, Extremely Inverse (I

2

t)

99-1377

BS, IEC Extremely Inverse (I

2

t)

G

G, Long Time Inverse (I

2

t)

99-1622

BS, IEC Long Time Inverse (I

2

t)

F

Fixed Time

N/A

N/A

Time Dial Setting Cross-Reference

Although the time characteristic curve shapes have been optimized for the DGC-2020, the DGC-2020
time dial settings are not identical to the settings of electromechanical induction disk overcurrent relays.
Table A-3 helps you convert the time dial settings of induction disk relays to the equivalent setting for the
DGC-2020.

Using Table A-3

Cross-reference table values were obtained by inspection of published electromechanical time current
characteristic curves. The time delay for a current of five times tap was entered into the time dial
calculator function for each time dial setting. The equivalent DGC-2020 time dial setting was then entered
into the cross-reference table.

If your electromechanical relay time dial setting is between the values provided in the table, it will be
necessary to interpolate (estimate the correct intermediate value) between the electromechanical setting
and the Basler Electric setting.

The DGC-2020 has a maximum time dial setting of 9.9. The Basler Electric equivalent time dial setting for
the electromechanical maximum setting is provided in the cross-reference table even if it exceeds 9.9.
This allows interpolation as noted above.

Basler Electric time current characteristics are determined by a linear mathematical equation. The
induction disk of an electromechanical relay has a certain degree of non linearity due to inertial and
friction effects. For this reason, even though every effort has been made to provide characteristic curves
with minimum deviation from the published electromechanical curves, slight deviations can exist between
them.

In applications where the time coordination between curves is extremely close, we recommend that you
choose the optimal time dial setting by inspection of the coordination study. In applications where
coordination is tight, it is recommended that you retrofit your circuits with Basler Electric electronic relays
to ensure high timing accuracy.